36
Switching output:
……………………………
Output is at
(TV = Threshold value)
• TV above = 1 | TV – Hyst. below = 0
• TV above = 0 | TV – Hyst. below = 1
• TV below = 1 | TV + Hyst. above = 0
• TV below = 0 | TV + Hyst. above = 1
Switching delay from 0 to 1
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
send periodically all
(only if sending “periodically”)
5 s • 10 s • 30 s • 1 min • … • 2 h
Blocking:
……………………………
Use block of the switching ouput
No • Yes
Evaluation of the blocking object
• if value 1: block | if value 0: release
• if value 0: block | if value 1: release
Value of the humidity blocking object
before 1. communication
0 • 1
Behaviour of switching output
with blocking
• do not send telegram
• send 0
• send 1
The behaviour with release of the switching output depends on the value of the
parameter “Switching output sends …” (see ”Switching output”)
Value of parameter
“Switching output sends”:
Setting options “Behaviour of Sswitching
output with release”:
on change
• do not send telegram
• send status of the switching output
on change to 1
• do not send telegram
• if switching output = 1
!
send 1
on change to 0
• do not send telegram
• if switching output = 0
!
send 0
on change and periodically
send status of the switching output
(no selection)
on change to 1 and periodically
if switching output = 1
!
send 1
(no selection)