11
No. Name
Function
DPT
Flags
60
Humidity threshold value 2: (1:+ | 0:-)
Input
1.006
C W
61
Humidity threshold value 2:
Switching output
Output
1.001
C R T
62
Humidity threshold value 2:
Switching output block
Input 1.006
C
W
63
Humidity control: Blocking object
Input
1.006
C W
64
Humidity control: Target value
Input / Output
9.007
C R W T U
65
Humidity control: Target value (1:+ | 0:-)
Input
1.006
C W
66
Humidity control: Act. variable
dehumidification 1. stage
Output
5.001
C R T
67
Humidity control: Act. variable
dehumidification 2. stage
Output
5.001
C R T
68
Humidity control: Act. variable
humidification
Output
5.001
C R T
69
Dew point temperature
Output
9.001
C R T
70
Cooling medium temp.: Threshold value
Output
9.001
C R W T U
71
Cooling medium temp.: Actual value
Input
9.001
C W
72
Cooling medium temp.:
Offset change (1:+ | 0:-)
Input 1.006
C
W
73
Cooling medium temp.: Switching output Output
1.001
C R T
74
Cooling medium temp.:
Switching output block
Input 1.006
C
W
75
Absolute humidity [g/kg]
Output
14.005
C R T
76
Absolute humidity [g/m³]
Output
14.005
C R T
77
Ambient climate:
1=comfortable | 0=uncomfortable
Output
1.006
C R T
78
Logic input 1
Input
1.006
C W
79
Logic input 2
Input
1.006
C W
80
Logic input 3
Input
1.006
C W
81
Logic input 4
Input
1.006
C W
82
Logic input 5
Input
1.006
C W
83
Logic input 6
Input
1.006
C W
Содержание KNX TH-UP basic