Hysteresis of the threshold value in %
0 … 50
Humidity switching output:
……………………………
Output is at
(TV = humidity threshold value)
• TV above = 1 | TV – Hyst. below = 0
• TV above = 0 | TV – Hyst. below = 1
• TV below = 1 | TV + Hyst. above = 0
• TV below = 0 | TV + Hyst. above = 1
Switching delay from 0 to 1
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
none • 1 s • 2 s • 5 s • 10 s • … • 2 h
Humidity switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Send humidity switching output
in the cycle of
(only if sending “periodically”)
5 s • 10 s • 30 s • 1 min • … • 2 h
Blocking:
……………………………
Use block of the humidity switching output
No • Yes
Evaluation of the humidity blocking object
• if value 1: block | if value 0: release
• if value 0: block | if value 1: release
Value of the humidity blocking object
before 1. communication
0 • 1
Behaviour of humidity switching output
with blocking
• do not send telegram
• send 0
• send 1
The behaviour with release of the switching output depends on the value of the
parameter “Humidity switching output sends …” (see ”Humidity switching output”)
Value of parameter
“Humidity switching output sends”:
Setting options “Behaviour of humidity
switching output with release”:
on change
• do not send telegram
• send status of the switching output
on change to 1
• do not send telegram
• if switching output = 1
!
send 1
on change to 0
• do not send telegram
• if switching output = 0
!
send 0