35
Cooling medium temperature sensor
This point only appears if “Use
monitoring of the cooling medium temperature: Yes
”
is
set in the dew point temperature menu.
Minumum cooling medium temperature threshold value:
……………………………
Threshold value = dew point tempe offset
The offset set last shall be
maintained
• not
• after restoration of voltage
• after restoration of voltage and programming
(Do not use for first commissioning)
Offset in °C
(only if the offset set last is “not” maintained
or “after restoration of voltage”)
0 … 20
Step size for offset change
per communication object
0.1°C • 0.2°C • 0.3°C • 0.4°C • 0.5°C • 1°C • 2°C •
3°C • 4°C • 5°C
Hysteresis of the threshold value in %
0 … 50
Threshold value
• do not send
• send periodically
• send in case of change
• send in case of change and periodically
From change of
(only if sending “in case of change”)
2% • 5% • 10% • 25% • 50%
Send periodically all
(only if sending “periodically”)
5 s • 10 s • 30 s • 1 min • … • 2 h