Setting the parameters
KNX eTR 205/206 Light push button
• Version: 16.12.2020 • Technical changes and errors excepted
If separate variables are used, select whether the variable of the 2nd stage is a 1-bit ob-
ject (on/off) or an 8-bit object (on with percentage value/off).
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
9.5.3. Fan Coil Control
The fan coil control enables the regulation of the fan of convector heating/cooling sys-
tems.
Activate the fan coil control.
In fan coil control, the fan is automatically controlled by one or, in multi-level systems,
several control variables for heating or cooling. Select which actuating variable(s) are
to control the output. The selection depends on the type of heating/cooling control and
the settings made for the actuating variables.
Select whether the first fan level should also be on when the second and third level are
running and whether the second fan level should also be on when the third level is run-
ning.
Set which mode is to be active after a reset.
Control variable is on
• 1-bit object
• 8-bit object
Value (in %)
(for 8-bit object)
0...100
When blocked, the control variable should
• not be sent
• send a specific value
Value (in %)
(only if a value is sent)
0...100
Use fan coil control
No •
Yes
Output is controlled via actuating variable
• Heating 1
• Heating 2
• Cooling 1
• Cooling 2
• Heating 1 and cooling 1
• Heating 2 and cooling 1
• Heating 1 and cooling 2
• Heating 2 and cooling 2
Switch Level 1 on also with Level 2 and 3
No • Yes
Switch Level 2 on also with Level 3
No • Yes
Mode after reset
• Manual
• Automatic (e.g. controller actuating
variable)