19
Setting the parameters
KNX eTR 205/206 Light push button
• Version: 16.12.2020 • Technical changes and errors excepted
A set threshold value will be retained until a new value or a change is transferred. The
current value is saved in so that it is retained in the event of a power supply failure and
will be available again once the power supply is restored.
Set the
hysteresis
independently of the type of threshold value setting.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setpoint using
Parameter •
Communication objects
The last communicated value should
• never
• after restoration of power
• after power restoration and
Programming
Start threshold value in 0.1°C
valid until first Communication
-300 … 800; 200
Object value limit (min)
in 0.1°C
-300…800
Object value limit (max)
in 0.1°C
-300…800
Type of threshold value change
Absolute value • Increase/decrease
Interval
(upon increase/decrease change)
0.1 °C • ... • 5°C
Hysteresis in % of the threshold value
0 … 50; 20
Hysteresis in 0.1°C
0 … 1100; 50
When the following conditions apply, the
output is
(TV = Threshold value)
• TV above = 1 | TV - Hyst. below = 0
• LV above = 0 |LV - hysteresis below = 1
• TV below = 1 |TV + hysteresis above = 0
• TV below = 0 |TV + hysteresis above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(if delay is adjustable via objects: valid until
1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(is sent only if "periodically" is selected)
5 s • 10 s • 30 s… • 2 h