Setting the parameters
KNX eTR 205/206 Light push button
• Version: 16.12.2020 • Technical changes and errors excepted
programming) is determined in the first section of "General controller". This also ap-
plies to a comfort extension.
The controller can be switched from eco mode, i.e. night mode, to comfort mode via
the comfort extension. This means that the comfort setpoint can be maintained for
longer, for example when having guests. The duration of this comfort extension period
is set. After the comfort extension period is terminated, the system returns to eco
mode.
Setpoint Comfort
Comfort mode is usually used for daytime mode when people are present. A starting
value is defined for the comfort setpoint as well as a temperature range in which the
nominal value may be modified.
If setpoint values are entered separately:
If the comfort setpoint value is used as a basis:
If the comfort setpoint is used as the basis, the increase/decrease of this value is indi-
cated.
If the comfort setpoint is used as the basis, a dead zone is determined for the control
mode "heating
and
cooling" to avoid direct switching from heating to cooling.
Grading for setpoint changes
(in 0.1 °C)
1… 50; 10
Storage of setpoint(s)
• not be retained
• after power restoration
• after restoration of power and program-
ming
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600
Initial heating/cooling setpoint (in 0.1 °C)
valid until first Communication
(not upon saving the target value after pro-
gramming)
-300…800; 210
Min. object value heating/cooling (in 0.1 °C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Minimum base setpoint (in 0.1°C)
-300…800; 160
Maximum base setpoint (in 0.1°C)
-300…800; 280
Reduction by up to (in 0.1°C)
1…100; 50
Increase by up to (in 0.1°C)
1…100; 50
Dead zone between heating and cooling
(only if both heating AND cooling are used)
1…100; 50