14
Channel setting in the ETS
Remote control Remo KNX RF
• Version: 14.02.2018 • Technical changes and errors excepted.
Temperature:
If the channel should be used to change the target temperature in the room, choose the
‘Temperature’ function and select whether the adjustment should take place via a bit object
or a temperature object.
In case of temperature adjustment via a
bit object
, only a 0 or a 1 is sent to the bus. Deter-
mine whether, after completing the temperature change, feedback should be sent to the re-
mote control.
In case of temperature adjustment via a
temperature object
the adjusted target temper-
ature value is sent. Set the size of the step for adjusting the value.
If is required that the feedback value is set up in the ETS. Without a feedback value, no new
target temperature value can be sent.
Scene:
If the channel should be used to call (and save) scenes, choose the ‘Scene’ function. Each
channel can control two scenes: one with the left button half, and one with the right button
half.
For the scene control, a group address for scenes must be filed in the KNX system. With
this group address, the output object ‘Channel X: scene A/B’ is linked to
Remo KNX RF
.
When calling or saving the scene, the scene number and, if any, the information are ‘saved’
and sent via the object. With the help of the group address, the actuators linked with the
address are sent to the scene inputs.
Number the scenes.
Determine if the scene can only be called or also be saved. The scene can be saved by hold-
Function
Temperature
Temperature change based on
• Bit object
• Temperature object
Temperature change based on
Bit object
Use feedback
No • Yes
Temperature change based on
Temperature object
Increment (in 0.1 °C)
0...100; 5
Function
Scene
Left/right button
Scenario No
0...63