39
Parameter setting
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
Input for temperature sensor T-NTC:
If a T-NTC temperature sensor is connected to the input, select the bus function "Tem-
perature sensor (NTC)" and set the following parameters for the measured value.
Choose whether a
Malfunction object
should be transmitted.
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired.
Note:
If an external portion is used, all of the following settings are related to the over-
all reading!
5.6.2. Control modes for drive control
If inputs are being used as switches to operate shades or windows, then various con-
trol modes can be set.
Standard:
If briefly operated, the drive will move incrementally or stops. If operated longer, the
drive will move up to the end position. The time difference between "short" and "long"
is set individually.
Use malfunction object
Yes • No
Offset in 0.1°C
-50…50; 0
Use external measured value
Yes • No
Ext. Reading proportion of the total reading
5% • 10% • ... • 50% • ... • 100%
Send behaviour
• periodically
• on change
• on change and periodically
On change of
(if sent on change)
0.1°C • ... • 0.5°C • ... • 5.0°C
Send cycle
(if sent periodically)
5 s • ... • 2 h
Control mode
• Standard
• Standard inverted
• Comfort mode
• Dead man’s switch
Control mode
Standard
Behavior during button operation:
short = stop/increment long = Up or Down
Time between short and long
in 0.1 seconds
1...50; 10