19
Transfer protocol
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
390
Temp. contr.5: Comfort
extension status
Input/
Output
RWCT
[1.1] DPT_Switch
1 bit
401
Temp. contr.6: Measured
value
Input
-WCT
[9.1] DPT_Val-
ue_Temp
2 bytes
402
Temp. contr.6: HVAC mode
(priority 1)
Input
-WC-
[20.102] DPT_HVAC-
Mode
1 byte
403
Temp. contr.6: HVAC mode
(priority 2)
Input
-WC-
[20.102] DPT_HVAC-
Mode
1 byte
405
Temp. contr.6: Mode frost/
heat protection activation
Input
-WC-
[1.1] DPT_Switch
1 bit
406
Temp. contr.6: Block
Input
-WC-
[1.1] DPT_Switch
1 bit
407
Temp. contr.6: Current
setpoint
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
408
Temp. contr.6: Switching
object (heating / cooling)
Input
-WC-
[1.1] DPT_Switch
1 bit
409
Temp. contr.6: Setpoint
comfort heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
410
Temp. contr.6: Setpoint
comfort heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
411
Temp. contr.6: Setpoint
comfort cooling
Input
output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
412
Temp. contr.6: Setpoint
comfort cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
413
Temp. contr.6: Setpoint
standby heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
414
Temp. contr.6: Setpoint
standby heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
415
Temp. contr.6: Setpoint
standby cooling
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
416
Temp. contr.6: Setpoint
standby cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
417
Temp. contr.6: Setpoint
eco heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
418
Temp. contr.6: Setpoint,
eco heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
419
Temp. contr.6: Setpoint
eco cooling
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
420
Temp. contr.6: Setpoint,
eco cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
421
Temp. contr.6: Control
variable stage 1
Output
R-CT
[5.1] DPT_Scaling
1 byte
422
Temp. contr.6: Control
variable stage 2
Output
R-CT
[5.1] DPT_Scaling
1 byte
No.
Text
Function
Flags
DPT type
Size