30
Parameter setting
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
The control may be manually reset to comfort mode from eco, or night mode. This al-
lows the user to maintain the daily nominal value for a longer time, e.g. when having
guests. The duration of this comfort extension period is set. After the comfort exten-
sion period is terminated, the system returns to eco mode.
Set point Comfort
Comfort mode is usually used for daytime mode when people are present. A starting
value is defined for the comfort set point as well as a temperature range in which the
nominal value may be modified.
If the comfort set point is used as the basis, a dead zone is determined for the control
mode "heating
and
cooling" to avoid direct switching from heating to cooling.
Set point for standby
Standby mode is usually used for daytime mode when people are absent.
If set point values are entered separately:
A starting set point value is defined as well as a temperature range in which the nom-
inal value may be modified.
If the comfort set point value is used as a basis:
If the comfort set point value is used as a basis, the deviation from this value is set.
Comfort extension time in seconds
(can only be activated from eco mode)
1…36000; 3600
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
not upon saving the set point value after
programming
-300…800; 210
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280
Dead zone between heating and cooling
only if both heating AND cooling are used.
1…100; 50
Initial heating/cooling set point (in 0.1 °C)
valid till 1st communication
-300…800; 210
Min. object value heating/cooling (in 0.1
°C)
-300…800; 160
Max. object value heating/cooling (in 0.1
°C)
-300…800; 280