36
Parameter setting
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the
threshold range. Then determine whether a 1 bit object (on/off) or an 8 bit object (on
with percentage/off) should be used.
Now determine what should be transmitted when the control is blocked.
Upon release, the control variable follows the rule again.
In case of a common variable for heating and cooling, 0 is always transmitted as a fixed
value.
5.6.
Interfaces
Activate the interfaces (inputs) that you want to use here. The
Temperature evalua-
tion unit KNX T6-UN-B4
provides four interfaces.
5.6.1. Interface 1...4
The interface inputs can be configured as switches, drive controller, dimmer, for trans-
mitting values and for the scenario recall. Alternatively a T-NTC sensor can be connect-
ed, so that further measured temperature values can be handed over to the bus.
Control type
is determined at a higher level for common
variables
•
2-point control
Hysteresis (in 0.1°C)
0…100; 20
Actuating variable is a
• 1-bit object
• 8-bit object
Value (in %)
only for 8 bit objects
0...100
When blocked, the variable shall
• not be transmitted
• send a specific value
Value (in %)
only if a value is transmitted
0...100
Use regulator values 1/2/3/4/5/6
Yes • No
Function
• Switch
• Changeover switch
• Shutter
• Roller blind
• Awning
• Window
• Dimmer
• 8-bit encoder
• 16-bit encoder
• Scenario recall
• Temperature sensor (NTC)