15
Transfer protocol
Temperature evaluation unit KNX T6-UN-B4
• Version: 17/12/2019 • Technical changes and errors excepted.
283
Temp. contr.3: HVAC mode
(priority 2)
Input
-WC-
[20.102] DPT_HVAC-
Mode
1 byte
285
Temp. contr.3: Mode frost/
heat protection activation
Input
-WC-
[1.1] DPT_Switch
1 bit
286
Temp. contr.3: Block
Input
-WC-
[1.1] DPT_Switch
1 bit
287
Temp. contr.3: Current
setpoint
Output
R-CT
[9.1] DPT_Val-
ue_Temp
2 bytes
288
Temp. contr.3: Switching
object (heating / cooling)
Input
-WC-
[1.1] DPT_Switch
1 bit
289
Temp. contr.3: Setpoint
comfort heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
290
Temp. contr.3: Setpoint
comfort heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
291
Temp. contr.3: Setpoint
comfort cooling
Input
output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
292
Temp. contr.3: Setpoint
comfort cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
293
Temp. contr.3: Setpoint
standby heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
294
Temp. contr.3: Setpoint
standby heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
295
Temp. contr.3: Setpoint
standby cooling
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
296
Temp. contr.3: Setpoint
standby cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
297
Temp. contr.3: Setpoint
eco heating
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
298
Temp. contr.3: Setpoint,
eco heating (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
299
Temp. contr.3: Setpoint
eco cooling
Input/
Output
RWCT
[9.1] DPT_Val-
ue_Temp
2 bytes
300
Temp. contr.3: Setpoint,
eco cooling (1:+ | 0: -)
Input
-WC-
[1.1] DPT_Switch
1 bit
301
Temp. contr.3: Control
variable stage 1
Output
R-CT
[5.1] DPT_Scaling
1 byte
302
Temp. contr.3: Control
variable stage 2
Output
R-CT
[5.1] DPT_Scaling
1 byte
303
Temp. contr.3: Control
variable cooling level 1
Output
R-CT
[5.1] DPT_Scaling
1 byte
304
Temp. contr.3: Control
variable cooling level 2
Output
R-CT
[5.1] DPT_Scaling
1 byte
305
Temp. contr.3: Status
heating level 1 (1=ON |
0=OFF)
Output
R-CT
[1.1] DPT_Switch
1 bit
No.
Text
Function
Flags
DPT type
Size