Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.
Block
The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.
Threshold value setpoint using
Parameter •
Communications objects
The last communicated value should be
retained
• never
• after restoration of power
• after restoration of power and
Programming
Start threshold value in 0.1°C
valid till 1st communication
-300 … 800; 200
Object value limit (min)
in 0.1°C
-300…800
Object value limit (max)
in 0.1°C
-300…800
Type of threshold change
Absolute value • Increase/decrease
Increment in 0.1
(upon increase/decrease change)
1...10000; 10
Hysteresis of the threshold value in %
0 … 50; 20
When the following conditions apply,
the output is
(TV = Threshold value)
• TV above = 1 | TV - Hyst. below = 0
• TV above = 0 | TV - Hyst. below = 1
• TV below = 1 |TV + hysteresis above = 0
• TV below = 0 |TV + hysteresis above = 1
Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay is set via objects: valid until 1st
communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay is set via objects: valid until 1st
communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends
• on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h