It is used to record the types of the most recent three faults of the AC drive. 0 Indicates no fault. For possible causes and solution
of each fault, refer to Chapter 5.
P9.17
Frequency upon 3rd fault
It displays the frequency when the latest fault occurs.
P9.18
Current upon 3rd fault
It displays the current when the latest
fault occurs.
P9.19
Bus voltage upon 3rd fault
It displays the bus voltage when the
latest fault occurs.
P9.20
Input terminal status upon 3rd fault
It displays the status of all input
terminals when the latest fault occurs. the sequence is as follows:
If an input terminal is ON, the setting is 1, the OFF is 0, the setting is
0. The value is the equivalent decimal number
converted from the S status.
P9.21
Output terminal status upon 3rd fault
It displays the status of ell output terminals when the latest fault
occurs. The sequence is as follows:
If an output terminal is ON, the setting is 1, the OFF is 0. If the
output terminal is OFF, the setting is 0.The value is the equivalent
decimal number converted
from the S statuses.
P9.22
AC drive status upon 3rd
fault
Reserved
P9.23
Power-on time upon 3rd fault
It displays the present power-on time when the latest fault occurs.
P9.24
Running time upon 3rd fault
It displays the present running time when the latest fault occurs.
P9.27
Frequency upon 2ndfault
Same as P9.17-P9.24
P9.28
Current upon2nd fault
P9.29
Bus voltage upon 2nd fault
P9.30
input terminal status upon 2nd fault
P9.31
Output terminal status upon
2nd fault
P9.32
AC drive status upon 2nd fault
P9.33
power-on time upon 2nd fault
P9.34
Running time upon 2nd fault
P9.37
Frequency upon 1st fault
Same as P9.17-P9.24
P9.38
Current upon 1st fault
Same as P9.17-P9.24
P9.39
Bus voltage upon 1st fault
P9.40
input terminal status upon 1st fault
P9.41
output terminal status upon
1st fault
P9.42
AC drive status 1st fault
P9.43
power-on time upon 1st fault
P9.44
Running time upon1st fault
P9.47
Fault protection action selection 1
Default
00000
Setting Range
Unit's digit
Motor overload (OL1)
0
Coast to stop
1
Stop according to the stop mode