P8.36
Output over current threshold
Default
200.0%
Setting Range
0.0% (no detection)
0.1% ~ 300.0% (rated motor current)
P8.37
Output over current detection delay time
Default
0.00s
Setting Range
0.00s ~ 600.00s
If the output current of the AC drive is equal to or higher than the over current threshold and the duration exceeds the detection
delay time, the corresponding M01 becomes ON. The output over current detection function is shown in the following figure.
P8.38
Any current reaching 1
Default
100.0%
Setting Range
0.0% ~ 300.0% (rated motor current)
P8.39
Any current reaching 1 amplitude
Default
0.0%
Setting Range
0.0% ~ 300.0% (rated motor current)
P8.40
Any current reaching 2
Default
100.0%
Setting Range
0.0% ~ 300.0% (rated motor current)
P8.41
Any current reaching 2 amplitude
Default
0.0%
Setting Range
0.0% ~ 300.0% (rated motor current)
If the output current of the AC drive is within the positive and negative amplitudes of any current reaching detection value, the
corresponding M01 becomes ON.
The ED2000 provides two groups of any current reaching detection parameters, including current detection value and detection
amplitudes, as shown in the following figure.
Figure 4-21 Any current reaching detection
P8.42
Timing function selection
Default
0
Setting Range
0
Disabled
1
Enabled