7
AC drive
overload pre-warning
The terminal outputs ON 10s before the AC drive overload protection action is
performed.
8
Set count value reached
The terminal outputs ON when the count value reaches the value set In Pb.08.
9
Designated count
value reached
The terminal outputs ON when the count value reaches the value set in Pb.09.
10
Length reached
The terminal outputs ON when the detected actual length exceeds the value set in
Pb.05.
11
PLC cycle complete
When simple PLC completes one cycle, the terminal outputs a pulse signal with width
of 250 ms.
12
Accumulative running
time reached
If the accumulative running time of the AC drive exceeds the time set in PS.17, the
terminal outputs ON.
13
Frequency limited
If the set frequency exceeds the frequency upper limit or lower limit and the output
frequency of the AC drive reaches the upper limit or lower limit, the
terminal outputs ON.
14
Torque limited
In speed control mode, if the output torque reaches the torque limit, the AC drive
enters the stall protection state and meanwhile the terminal outputs
ON.
15
Ready for RUN
If the AC drive main circuit and control circuit become stable, and the AC drive detects
no fault
and is ready for RUN, the terminal outputs ON.
16
FIV>FIC
When the input of FIV is larger than the input of FIC, the terminal outputs ON.
17
Frequency upper
limit reached
If the running frequency reaches the upper limit, the
terminal outputs ON.
18
Frequency lower limit
reached (no output at
stop)
If the running frequency reaches the lower limit, the terminal becomes ON. In the stop
state, the terminal outputs OFF.
19
Under voltage stats output If the AC drive is in under voltage state, the terminal outputs ON.
20
Communication
setting
Refer to the communication protocol.
21
Reserved
Reserved
22
Reserved
Reserved
23
Zero-speed running 2 (having
output at
stop)
If the output frequency of the AC drive is 0, the terminal becomes ON. In the state of
stop, the signal is still ON.
24
Accumulative power-
on time reached
If the AC drive accumulative power-on time (P7.13) exceeds the value set in PB.16, the
terminal
becomes ON.
25
Frequency level detection
FDT2 output
Refer to the descriptions ofPB.28 and PS.29.
26
Frequency 1 reached output Refer to the descriptions ofPB.30 and PS.31.
27
Frequency2
reached output
Refer to the descriptions ofPB.32 and PB.33.
28
Current 1 reached output Refer to the descriptions of PB.38 and PB.39.
29
Current 2 reached output Refer to the descriptions of PB.40 and PB.41.
30
Timing reached output
If the timing function (PB.42) is valid, the terminal becomes ON after the current
running time of the
AC drive reaches the set time.