P8.43
Timing duration
source
0: P8.44
1: FIV
2: FIC
3: reserved
100% of analog input corresponds to the value of P8.44
0
☆
P8.44
Timing duration 0.0Min-6500.0Min
0.0Min
☆
P8.45
FIV input voltage
lower limit
0.00V-P8.46
3.10V
☆
P8.46
FIV input
voltage upper limit
P8.45 ~ 10.00V
6.80V
☆
P8.47
Module
temperature
threshold
0⁰C ~ 150⁰C
100⁰C
☆
P8.48 Cooling fan control
0: Fan working during running
1: Fan working continuously
0
☆
P8.49
Wakeup
frequency
Dormant frequency (P8.51 )
~ maximum frequency (P0.12 )
0.00Hz
☆
P8.50
Wakeup delay
time
0.0s ~ 6500.0s
0.0s
☆
P8.51
Dormant
frequency
0.00Hz ~ wakeup frequency (P8.49)
0.00Hz
☆
P8.52
Dormant delay
time
0.0s ~ 6500.0s
0.0s
☆
P8.53
Current running
time reached
0.0Min ~ 6500.0Min
0.0Min
★
Group P9: Fault and Protection
P9.00
Motor overload
protection
selection
0: Disabled
1: Enabled
1
☆
P9.01
Motor overload
protection gain
0.20 ~ 10.00
1.00
☆
P9.02
Motor overload
warning
coefficient
50% ~ 100%
80%
☆
P9.03
Overvoltage stall
gain
0 ~ 100
0
☆
P9.04
Overvoltage stall
protective voltage
120% ~ 150%
130%
☆
P9.05
Over current stall
gain
0 ~100
20
☆
P9.06
Over current stall
protective current
100% ~ 200%
150%
☆
P9.07
Short-circuit to
ground upon
power-on
0: Disabled
1: Enabled
1
☆
P9.09
Fault auto reset
times
0 ~ 20
0
☆