Function
Code
Parameter
Name
Setting Range
Default
Property
P9.43
Output terminal
status upon 1st
fault
-
-
•
P9.44
Frequency upon
1st fault
-
-
•
P9.47
Fault protection
action selection 1
Unit's digit: Motor overload(OL1)
0:Coast to stop
1:Stop according to the stop mode
2:Continue to run
Ten's digit: Reserved
Hundred's digit: Power output phase loss(LO)
Thousand's digit: External equipment fault(EF)
Ten thousand's digit: Communication fault(CE)
00000
☆
P9.48
Fault protection
action selection 2
Unit's digit: Reserved
0:Coast to stop
Ten's digit: EEPROM read-write fault(EEP)
0:Coast to stop
1:Stop according to the stop mode
Hundred's digit: Reserved Thousand's digit: Reserved
Ten thousand's digit: Accumulative running time reached (END1)
00000
☆
P9.49
Fault protection
action selection 3
Unit's digit: reserved
Unit's digit: Reserved
0:Coast to stop
1:Stop according to the stop mode
2:Continue to run
Ten's digit: Reserved
0:Coast to stop
1:Stop according to the stop mode
2:Continue to run
Hundred's digit: Accumulative power-on time reached (END2) 0:Coast to
stop
1:Stop according to the stop mode
2:Continue to run
Thousand's digit: Load becoming 0
0:Coast to stop
1:Stop according to the stop mode
2:Continue to run at 7% of rated motor frequency and resume to the set
frequency if the load recovers
Ten thousand's digit: PID feedback loss of running
0:Coast to stop
1:Stop according to the stop mode
2:Continue to run
00000
☆
P9.50
Reserved
☆
P9.54
Frequency
selection for
continuing to run
0:Current running frequency
1:Set frequency
2:Frequency upper limit
3:Frequency lower limit
4:Backup frequency upon abnormality
0
☆