PID setting source
Default
0
Setting Range
0
PA.01
1
FIV
2
FIC
3
Reserved
4
PULSE setting (S3)
5
Communication setting
6
Multi-reference
PA.01
PIO digital setting
Default
50.0%
Setting Range
0.0% ~ 100.0%
PA.00 is used to select the channel of target process PID setting. The PID setting is a relative value and ranges from 0.0% to 100.0%.
The PID feedback is also a relative value. The purpose of PID control is to make the PID setting and PID feedback the same.
PA.02
PID feedback source
Default
0
Setting Range
0
FIV
1
FIC
2
Reserved
3
FIV-FIC
4
PULSE setting (S3)
5
Communication setting
6
FIV+FIC
7
MAX ( |FIV|, |FIC|)
8
MIN ( |FIV|, |FIC|)
This parameter is used to select the feedback signal channel of process PID. The PID feedback is a relative value and ranges from
0.0% to 100.0%.
PA.03
PID action direction
Default
0
Setting Range
0
Forward action
1
Reverse action
0: Forward action
When the feedback value is smaller than the PID setting, the AC drive's output frequency rises. For example, the winding tension
control requires forward PID action.
1: Reverse action
When the feedback value is smaller than the PID setting, the AC drive's output frequency reduces. For example, the unwinding
tension control requires reverse PID action. Note that this function is influenced by reversing the multifunction terminal PID action.
Pay attention in the application.