79
CHAPTER 6 - DIAGNOSTICS AND TROUBLESHOOTING
(Flashing)
Inverter is powered up and is ready
A fault has been detected
The Error LED flashes, indicating
the number of the fault code
Example: E04
0.2 s
0.6 s
Power
LED
Error LED
Description
6.2 TROUBLESHOOTING
Table 6.2
- Meaning of LEDs indication for drive status
Off
On
On
references” at P120 has been enabled), the occurred fault
number, the status of the integrator of the IxT function
(overcurrent).
E24: indicates the fault code on the LED display.
E31: inverter proceeds to operate normally, but it does not
accept the keypad commands; the fault code is indicated
on the LED display.
E41: does not allow inverter operation (it is not possible to
enable the inverter); the fault code is indicated on the LED
display and on the “ERROR” LED.
Indication on the Inverter Status LEDs:
PROBLEM
POINT TO BE
CORRECTIVE ACTION
CHECKED
Motor does not run
Incorrect wiring
1.Check the power and the control connections. For example,
the digital inputs DIx programmed for Start/Stop or General Enable
or No External Fault must be connected to GND (pin 5 of the
control connector XC1)
Analog reference
1.Check if the external signal is properly connected
(if used)
2.Check the status of the speed potentiometer (if used)
Incorrect Programming 1.Check if the parameters are properly programmed for the
application
Fault
1.Check if the inverter has not been disabled due to detected fault
condition (refer to item 6.1)
Motor Stall
1.Reduce the motor load
2.Increase P169 or P136/P137
Motor speed varies
Loose connections
1.Disable the inverter, switch OFF the power supply and tighten all
(oscillates)
connections
Defective speed
1.Replace the defective speed potentiometer
potentiometer
Variation of the external 1.Identify the cause of the variation
analog reference
Table 6.3
- Solution for the most frequent problems
Содержание EWCFW-08
Страница 2: ......
Страница 6: ......
Страница 86: ......
Страница 88: ......
Страница 146: ......
Страница 218: ......
Страница 220: ......
Страница 233: ...233 KAPITEL 3 INSTALLATION Bild 3 1 Montageabmessungen des CFW 08 MONTAGEABMESSUMGEN FRONT ANSICHT SEITEN ANSCICHT...
Страница 270: ......
Страница 272: ......
Страница 284: ...284 CHAPITRE 3 INSTALLATION Figure 3 2 Sch ma dimensionnel de CFW 08 VUE DU BAS DU MONTAGE VUE DE FACE VUE LAT RALE...