8
CFW-08 - QUICK PARAMETER REFERENCE
Parameter
Function
Adjustable Range
Factory
Unit
User
Page
Setting
Setting
(*)
The factory default of parameter P136 depends on the inverter model as follows:
- models 1.6-2.6-4.0-7.0 A/200-240 V and 1.0-1.6-2.6-4.0 A/380-480 V: P136 = 5.0 %;
- models 7.3-10-16 A/200-240 V and 2.7-4.3-6.5-10 A/380-480 V: P136 = 2.0 %;
- models 22-28-33 A/200-240 V and 13-16-24-30 A/380-480 V: P136 = 1.0 %.
Speed Limits
P133
Minimum Frequency (F
min
)
0.00 to P134
3.00
Hz
P134
Maximum Frequency (F
max
)
P133 to 300.0
66.00
Hz
V/F Control
P136
(2) (*)
Manual Torque Boost
0.0 to 30.0
5.0 or
%
(IxR Compensation)
2.0 or
1.0
(*)
P137
(2)
Automatic Torque Boost
0.00 to 1.00
0.00
-
(Automatic IxR Compensation)
P138
(2)
Slip Compensation
0.0 to 10.0
0.0
%
P142
(2) (3)
Maximum Output Voltage
0 to 100
100
%
P145
(2) (3)
Field Weakening
P133 to P134
50.00 Hz or
Hz
Frequency (F
nom
)
60.00 Hz
depending
on the
market
DC Link Voltage Regulation
P151
DC Link Voltage Regulation
200 V models: 325 to 410
380
V
Level
400 V models: 564 to 820
780
Overload Current
P156
Motor Overload Current
0.2xI
nom
to 1.3xI
nom
1.2xP401
A
Current Limitation
P169
Maximum Output Current
0.2xI
nom
to 2.0xI
nom
1.5xP295
A
Flux Control
P178
(1)
Rated Flux
50.0 to 150
100
%
CONFIGURATION PARAMETERS - P200 to P398
Generic Parameters
P202
(3)
Control Mode
0 = Linear V/F Control
0
-
(Scalar)
1 = Quadratic V/F Control
(Scalar)
2 = Sensorless Vector Control
P203
(3)
Special Function Selection
0 = No function
0
-
1 = PID Regulator
P204
(3)
Load Factory Setting
0 to 4 = No Function
0
-
5 = Loads Factory Default
P205
Display Default Selection
0 = P005
2
-
1 = P003
2 = P002
3 = P007
4, 5 = Not Used
6 = P040
P206
Auto-Reset Time
0 to 255
0
s
P208
Reference Scale Factor
0.00 to 99.9
1.00
-
P212
Frequency to Enable the Sleep 0.00 to P134
0.00
Hz
Mode
P213
Time Delay to Activate the
0.1 to 999
2.0
s
Sleep Mode
P215
(3) (4)
Keypad Copy Function
0 = Not Used
0
-
1 = Copy (inverter
keypad)
2 = Paste (keypad
inverter)
P219
(3)
Switching Frequency
0.00 to 25.00
6.00
Hz
Reduction Point
Содержание EWCFW-08
Страница 2: ......
Страница 6: ......
Страница 86: ......