77
CHAPTER 6 - DIAGNOSTICS AND TROUBLESHOOTING
E02
Power-on
Power supply voltage too low, causing a DC link
DC link
Manual (key
)
voltage lower than the minimum allowed value (read the
undervoltage
Auto-reset
value in parameter P004)
DI
Ud < 200 V - 200 - 240 V models
Ud < 360 V - 380 - 480 V models
E04
Ambient temperature too high (> 40
o
C [104 ºF]) and/or
Overtemperature
output current too high
at the power
Blower locked or defective
heatsink or in the
inverter internal air
E05
P156 set too low for the motor that is being used
Motor/inverter
Too much load on motor shaft
overload
Ixt function
E06
Any DI programmed for external fault
External fault
detection is open (not connected to GND - XC1)
E08
Electrical noise
CPU error
(Watchdog)
E09
Contact Eliwell
Memory with corrupted values
Program memory
error (Checksum)
E10
Power-on
Defective contact in the HMI-CFW08-RS cable
Keypad copy
Manual (key
)
Electrical noise in the installation (electromagnetic
function error
Auto-reset
interference)
DI
E14
Power-on
Motor is not connected to the inverter output
Self-tuning
Manual (key
)
Wrong motor connection (wrong voltage, lack of one
routine error
Self-tuning routine error phase)
The used motor is too small for the inverter
(P401 < 0.3 x P295). Use V/Fcontrol
The value of P409 (stator resistance) is too high for the
used inverter
E22
-
Serial communication error
Serial
communication
error
E24
It is automatically reset
Incompatible parameters were programmed
Programming
when the incompatible
Refer to table 4.1
error
parameters are changed
E25
-
Serial communication error
Serial
communication
error
E26
Serial
communication
error
Table 6.1 (cont.)
- Errors, possible causes and reset ways
FAULT
RESET
(1)
POSSIBLE CAUSES
Содержание EWCFW-08
Страница 2: ......
Страница 6: ......
Страница 86: ......
Страница 88: ......
Страница 146: ......
Страница 218: ......
Страница 220: ......
Страница 233: ...233 KAPITEL 3 INSTALLATION Bild 3 1 Montageabmessungen des CFW 08 MONTAGEABMESSUMGEN FRONT ANSICHT SEITEN ANSCICHT...
Страница 270: ......
Страница 272: ......
Страница 284: ...284 CHAPITRE 3 INSTALLATION Figure 3 2 Sch ma dimensionnel de CFW 08 VUE DU BAS DU MONTAGE VUE DE FACE VUE LAT RALE...