Programming
4
© ELETTROQUADRI S.r.l.
26 / 66
INSTALLATION MANUAL
AC
0 to UP
left dot = front
accesses
right dot = rear
PF
0 to UP
fireman floor
tF
00-07
fireman protocol
fireman manoeuvre protocol (see fireman
table)
rF
no
at fireman floor only
return from fireman manoeuvre mode
yes
to any floor
PE
0 to UP
evacuation floor
tE
00-07
evacuation protocol
evacuation manoeuvre protocol (see
fireman table)
rE
no
at evacuation floor only
return from evacuation manoeuvre mode
yes
to any floor
FS
0 to UP
out of service parking floor
PA
PP+1 to UP
-- = not defined
alternative parking (duplex only)
PS
0 to UP
left dot = front
skip floors and accesses (duplex only)
right dot = rear
PU
0 to UP
left dot = selected
special floors and accesses (duplex only) (the
button of the select floor calls its own car)
Pc
no
park with doors open
doors parked (MP3 only)
yes
park with doors closed
CP
0 to UP
left dot = front
floors and accesses with doors closed
parking (with Pc = ON)
right dot = rear
IP
no
park at last served floor
send to parking
yes
sends to parking
nA
no
normal
block doors opening for testing
yes
does not open the doors
dG
no
standard control panels
selection for systems with DMG control
panel
yes
DMG control panel
(*)
In
no
not active
call interdiction (only duplo = SAPB duplex)
yes active
MP3