Example: you want to connect a 15 kW unit and a 3kW unit in order to achieve 18 kW. Generally, the voltage rating must match,
but current and power rating can be different. To be precise, the power rating is decisive. When using the 3 kW unit as master,
the total system power will only be 15.75 kW (with a master running firmware KE 3.02). When, however, switching the master
to the 15 kW unit, the system will result in 18 kW total power.
3.11.1.6
Configuring the master-slave operation
Now the master-slave system has to be configured on each unit. It’s recommended to configure all the slave units first and
then the master unit.
►
Step 1: Configuring all slave units
1.
While the DC output is switched off, tap on
in the main screen to access the
Settings
menu. Swipe up to find
group
Master-slave
and tap it.
2.
Tapping on the blue button text next to
Mode
will open a selector. By selecting
Slave
, if not already set, the master-slave
mode is activated and the device is defined as slave. Additionally, the bus termination can be activated here, if required
for the currently configured unit.
3.
Leave the Settings menu.
After this, the slave is fully configured for master-slave. Repeat the procedure for all other slave units.
►
Step 2: Configuring the master unit
1.
While the DC output is switched off, tap on
in the main screen to access the
Settings
menu. Swipe up to find
group
Master-slave
and tap it.
2.
Tapping on the blue button text next to
Mode
will open a selector. By selecting
Master
, if not already set, the master-slave
mode is activated and the device is defined as master which also automatically enable the BIAS resistor termination,
as required for the master.
►
Step 3: Initializing the master
When setting a device to Master, it will instantly start to initialize the MS system and the result is displayed in the very same
window. In case the initialization is not successful or the number of units or the total power is wrong, it can be repeated in
this screen anytime.
Tapping
Initialize system
repeats the search for slaves in case the
detected number of slaves is less than expected, the system has been
reconfigured, not all slave units are already set as
Slave
or the cabling/
termination is still not OK. The result window shows the number of
slaves plus the total current, power and resistance of the MS system.
In case there are no slaves found at all, the master will still initialize the
MS system with only itself.
As long as MS mode remains activated, the initialization process of the master-slave system will be re-
peated each time the master unit is powered. The initialization can also be repeated manually anytime via
the Settings menu, in group “Master-Slave”.
3.11.1.7 Operating the master-slave system
After successful configuration and initialization of the master and slave units, they will show their status in the in the status
area of their displays. The master would show
MS mode: Master
while the slave(s) would show
MS mode: Slave
plus
Remote:
Master-slave
, as long they are in remote control from the master.
From now on the slaves can no longer be controlled manually or remotely, neither via the analog nor via digital interfaces.
They can, if needed, be monitored via these interfaces by reading actual values and status.
The display on the master unit will reconfigure after initialization and all set values are reset. The master now displays the set
and actual values of the total system. Depending on the number of units, the adjustable current and power range will multiply,
while the resistance range will decrease. Then following applies:
•
The system, represented by the master, can be treated like a standalone unit
•
The master shares the set values etc. across the slaves and controls them
•
The master is remotely controllable via the analog or digital interfaces
•
All settings for the set values U,I, P and R on the master, plus also all related values from supervision, limits etc. should be