© EA Elektro-Automatik in 2022, this information is subject to change without notice
48
06230920_manual_ps_10000_3u_15kw_en_01
Group
Parameters & description
Timeouts
TCP keep-alive
Activates keep-alive network functionality for the Ethernet port, which is used to keep the socket
connection open. As long as keep-alive is valid in the network, the device will disable the Ethernet
timeout. Also see below at “Timeout ETH”.
Timeout USB/RS232
Defines the max. time between two subsequent bytes or blocks of a transferred message. For more
information about the timeout refer to the external programming documentation “Programming
Guide ModBus & SCPI”. Default value:
5 ms
, Range: 5...65535
Timeout ETH
Defines a timeout after which the device would close the socket connection if there was no com
-
mand communication between the controlling unit (PC, PLC etc.) and the device for the adjusted
time. The timeout is ineffective as long as option
TCP keep-alive
is enabled for the particular
interface and the keep-alive network service is running. A setting of 0 would deactivate the timeout
permanently. Default value:
5 s
, Range: 0 / 5...65535 (0 = timeout deactivated)
Interface monitoring / Timeout Interface monitoring
Activates/deactivates the interface monitoring (see section
“3.5.3.3. Interface monitoring“).
Default values: off,
5 s
/ Range: 5..65535
Protocols
Communication protocols
Enables or disables SCPI or ModBus communication protocols for the device. The change is im-
mediately effective. Only one of both can be disabled.
ModBus specification compliance
Allows to switch from
Limited
(default setting) to
Full
which makes the device send messages in
ModBus RTU or ModBus TCP format which fully comply to the specification and are compatible to
softwares available on the market. With
Limited
the device would still use the old, partially wrong
message format (see programming guide for details).
3.4.3.6 Menu “HMI Setup”
These settings refer exclusively to the control panel (HMI).
Group
Parameters & description
Language
Selection of the display language (default: English)
Sound
Key sound
Activates or deactivates sounds when touching a touch area in the display. It can usefully signal
that the action has been accepted.
Alarm sound
Activates or deactivates the additional acoustic signal of an alarm
.
See also
Clock
Internal clock and date setup
Backlight
Backlight off after 60s
The choice here is whether the backlight remains permanently on (default) or if it should go off
when no input via screen or rotary knob is done for 60 s. As soon as there is input, the backlight
returns automatically. Furthermore, the backlight intensity can be adjusted here.
Lock
“3.8. Locking the adjustment limits and user profiles“
and