© EA Elektro-Automatik in 2022, this information is subject to change without notice
11
06230920_manual_ps_10000_3u_15kw_en_01
1.8.3
Specific technical data
General specifi cations
AC Input
Voltage, Phases
208 V / 380 V / 400 V / 480 V ±10%, 3ph AC (208 V 3ph AC with Derating to 3 / 6 / 9 kW)
Frequency
45 - 66 Hz
Power factor
>0.99
Leakage current
<5 mA
Overvoltage category
2
Pollution degree
2
DC Output static
Load regulation CV
≤0.05% FS
(0 - 100% load, constant input voltage and constant temperature)
Line regulation CV
≤0.01% FS
(208 V - 480 V AC +10% input voltage, constant load and constant temperature)
Stability CV
≤0.02% FS
(Over 8hrs interval following 30 minutes warm-up, constant input voltage, load and temperature)
Temperature coeffi cient
CV
≤30ppm/°C
(Following 30 minutes warm up)
C
ompensation (Remote Sense)
≤5% U
Nominal
Load regulation CC
≤0.1% FS
(0 - 100% load, constant input voltage and constant temperature)
Line regulation CC
≤0.01% FS
(208 V - 480 V AC +10% input voltage, constant load and constant temperature)
Stability CC
≤0.02% FS
(Over 8hrs interval following 30 minutes warm-up, constant input voltage, load and temperature)
Temperature coeffi cient
CC
≤50ppm/°C
(Following 30 minutes warm up)
Load regulation CP
≤0.3% FS
(0 - 100% load, constant input voltage and constant temperature)
Load regulation CR
≤0.3% FS + 0.1% FS current
(0 - 100% load, constant input voltage and constant temperature)
Protective functions
OVP
Overvoltage protection
adjustable, 0 - 110% U
Nominal
OCP
Overcurrent protection
adjustable, 0 - 110%
I
Nominal
OPP
Overpower protection
adjustable, 0 - 110%
P
Nominal
OT
Overtemperature protection,
output shuts down in case of insuffi cient cooling
DC Output dynamic
Rise time 10 - 90% CV
≤20 ms
Fall time 90 - 10% CV
≤20 ms
Rise time 10 - 90% CC
≤10 ms
Fall time 90 - 10% CC
≤10 ms
Display accuracy
Voltage
≤0.05% FS
Current
≤0.1% FS
Insulation
AC Input to DC Output
3750 Vrms (1 Minute), creepage distance >8 mm
AC Input to case (PE)
2500 Vrms
DC Output to case (PE)
Depending on the model, see model table
DC Output to Interfaces
1000 V DC (Model up to 360 V output), 1500 V DC (Model from 500 V output)
Interfaces digital
Built-in, galvanically isolated
USB, Ethernet (100 MBit) for communication
1x USB Host
for data acquisition
Optional, galvanically isolated
CAN, CANopen, RS232, ModBus TCP, Profi net, Profi bus, EtherCAT, Ethernet
Interfaces analog
Built-in, galvanically isolated
15-pole D-Sub
Signal
range
0 - 10 V or 0 - 5 V (
switchable
)
Inputs
U, I, P, R,
remote control on/off, DC output on/off, resistance mode on/off
Outputs
Monitor U and I, alarms, reference voltage, status DC, status CV/CC
Accuracy
U / I / P / R
0 - 10 V ≤0.2%, 0 - 5 V ≤0.4%
Device confi guration
Parallel operation
Up to 64 units of any power class in series 10000, with Master-Slave-Bus and Share-Bus