Installation Manual
WARNING:
To reduce the risk of injury, use the
recommended wire size. It is very important for system
safety and efficient operation to use the appropriate wire
for grid (utility) connection.
WARNING:
To prevent the risk of electric shock, make sure
the ground wire is properly earthed before operating this
unit whether the grid is connected or not.
CAUTION:
Make sure the AC Load and AC Grid are properly
connected. Misconnecting them will damage the product.
WARNING:
Backup load terminals are to be wired to a
separate subpanel. Never connect backup load lines directly
to the main service panel without use of an external
automatic transfer switch. Direct connection of backup
loads output to the grid will result in damage to the
inverter.
WARNING:
Make
sure the circuit breaker is off before
making or modifying any connections.
WARNING:
Do not connect backup loads output in parallel
with the grid!
CAUTION:
Before making the final connection or closing
the breaker, make sure the connections have the correct
polarity. Check polarity labels.
CAUTION:
Do
NOT
apply anti-oxidant substance on the
terminals before terminals are connected tightly.
WARNING:
Check positive (+) and the negative (-)
terminals. If the PowerPod 2 is connected with reversed
polarity, unexpected reactions may occur such as damages,
heat generation, smoke, fire, or explosion.
WARNING:
Do not connect between the positive (+) and
negative (-) terminals with a conductive material (e.g. wire,
a cable, etc.). This may result in damages, heat generation,
smoke, fire, or explosion.
Safety Warnings
CAUTION:
Exceeding the maximum input voltage can
destroy the unit. Check the PV string voltage before wiring
the connection.