12-44
CONTROL SYSTEM
Revision Y06-01
Service Manual - LEX
12B.3.3 I FEEL
x
The switchover between RCT by the remote controller and RT detected by the
control board can be done by “I FEEL” function. After receiving the “I FEEL”
command from the remote controller, MCU decide the operation mode of the
air-conditioner by RCT detected by the remote controller.
x
In I-Feel Mode, IF I-Feel data hasn’t been received from the R/C for more than
4 minutes, the I-Feel Mode would be suspended and the Room Temperature is
replaced by the RT from the local sensor. As soon as new I-FEEL data is
received from the R/C, the I-FEEL Mode will be resumed.
12B.3.4
E.S.F and Ionizer
x
E.S.F and Ionizer will turn on when receiving a signal from the R/C. and IFAN
on.
12B.3.5
Fresh-
Air
Function
x
Fresh-Air has two ways: continuous and Auto.
x
If the Fresh-Air signal from R/C is continuous, Fresh-Air is on till the signal is
changed.
x
If the Fresh-Air signal from R/C is Auto, Fresh Air will turn on for 20 minutes
and then stop for 20 minutes, it continues doing cycle by cycle till the signal is
changed.
12B.3.6
EEPROM
x
The data stored in the EEPROM include:
x
the setting parameters, such as: on/off status, temperature, fan speed, mode,
louvers auto or fix, E.S.F , Ionizer, Fresh air, Timer status, Filter hour
Содержание LEX 12
Страница 36: ...9 1 ELECTRICAL CONNECTIONS Revision Y06 01 Service Manual LEX 9 ELECTRICAL CONNECTIONS 9 1 LEX 7 9 12 14 R410A ...
Страница 38: ...10 2 REFRIGERATION DIAGRAMS Revision Y06 01 Service Manual LEX 10 1 2 LEX 9 12 14 R410A ...
Страница 91: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 3 Outdoor Unit ONG 7 9 12 ST ...
Страница 95: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 7 Outdoor Unit ONG 14 ST ...
Страница 97: ...14 9 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 9 Outdoor Unit ONG 7 RC ...
Страница 99: ...14 11 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 11 Outdoor Unit ONG 9 12 RC ...
Страница 102: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 14 Outdoor Unit ONG 14 RC ...
Страница 106: ...15 3 OPTIONAL ACCESSORIES Revision Y06 01 Service Manual LEX 15 3 RCW RCW2 Wiring Connections as Shown on Kit ...
Страница 108: ......