12-37
CONTROL SYSTEM
Revision Y06-01
Service Manual - LEX
12B.2.5
High Pressure Protection (Excluding cooling only unit type)
OCT (ºC)
66
61
55
52
>= 3 min
COMP Any
Off
OFAN follows COMP OFAN FORCED ON
OFAN Any
On
LOW LOW
IFAN Any
LOW
x
If (OCT >= 61ºC), IFAN is forced to LOW. If (OCT <= 55ºC), IFAN restore to
normal.
x
If (OCT >= 66ºC), COMP stop and OFAN is forced on. If (OCT <= 52ºC),
COMP and OFAN will restore to normal operation.
Note: If OCT is invalid, high pressure protection cannot be activated.
12B.2.6 Fan
Mode
x
S.P.T range: 16ºC~30ºC. Initial: 24ºC;
x
IFAN speed range: Auto, Low, Mid and Hi. Initial speed: High;
x
If IFAN is set to Auto Fan, the IFAN will run at Low speed;
x
IFAN is always on, COMP, OFAN, AHEAT, RV are always off.
Содержание LEX 12
Страница 36: ...9 1 ELECTRICAL CONNECTIONS Revision Y06 01 Service Manual LEX 9 ELECTRICAL CONNECTIONS 9 1 LEX 7 9 12 14 R410A ...
Страница 38: ...10 2 REFRIGERATION DIAGRAMS Revision Y06 01 Service Manual LEX 10 1 2 LEX 9 12 14 R410A ...
Страница 91: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 3 Outdoor Unit ONG 7 9 12 ST ...
Страница 95: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 7 Outdoor Unit ONG 14 ST ...
Страница 97: ...14 9 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 9 Outdoor Unit ONG 7 RC ...
Страница 99: ...14 11 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 11 Outdoor Unit ONG 9 12 RC ...
Страница 102: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 14 Outdoor Unit ONG 14 RC ...
Страница 106: ...15 3 OPTIONAL ACCESSORIES Revision Y06 01 Service Manual LEX 15 3 RCW RCW2 Wiring Connections as Shown on Kit ...
Страница 108: ......