12-10
CONTROL SYSTEM
Revision Y06-01
Service Manual - LEX
12.6.3 HE
operation
•
For
all Groups
, HE can be ON only when IFAN is ON.
•
For
all Groups
, HE switches to OFF when ICT > 50
o
c, and is activated
again when ICT
≤
45
o
c.
•
In
SH or RC group
, HE operation is limited by the following graph:
•
Back-up mode for
SH group
After COMP has been working for 5 minutes, HE & IFAN are activated even
if the ICT is still below 35
o
c. This situation is called Back-up Mode. Both
HE & IFAN will work in Back-up Mode until the ICT reaches 35
o
c. Then, the
operation goes on in the usual mode .
HE
ON
OFF
30
45
50
ICT [
o
c]
15
General :
For WAX :
35
20
40
Содержание LEX 12
Страница 36: ...9 1 ELECTRICAL CONNECTIONS Revision Y06 01 Service Manual LEX 9 ELECTRICAL CONNECTIONS 9 1 LEX 7 9 12 14 R410A ...
Страница 38: ...10 2 REFRIGERATION DIAGRAMS Revision Y06 01 Service Manual LEX 10 1 2 LEX 9 12 14 R410A ...
Страница 91: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 3 Outdoor Unit ONG 7 9 12 ST ...
Страница 95: ...14 7 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 7 Outdoor Unit ONG 14 ST ...
Страница 97: ...14 9 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 9 Outdoor Unit ONG 7 RC ...
Страница 99: ...14 11 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 11 Outdoor Unit ONG 9 12 RC ...
Страница 102: ...14 14 EXPLODED VIEWS AND SPARE PARTS LISTS Revision Y06 01 Service Manual LEX 14 1 14 Outdoor Unit ONG 14 RC ...
Страница 106: ...15 3 OPTIONAL ACCESSORIES Revision Y06 01 Service Manual LEX 15 3 RCW RCW2 Wiring Connections as Shown on Kit ...
Страница 108: ......