7
MECHANICAL
M1/1
PISCES
MINIFILL
9.1
Wiring Details
Drawn by:
Date:
Title.
Version:
Drg Nr
Pages:
1.1
MHS 1.1
1
Jim Wyborn
27
th
August 2015
Elco Heat ing Solutions
3 Juniper West, Fenton Way
Southfields Business Park
Basildon, Essex
SS15 6SJ Tel 01268 546700
Pisces
Minifill Wiring
Mechanical
1
2
3
4
5
6
7
8
9
10
11
12
Healthy
Healthy
Live from Pressure
Switch
Input
Input
Live to Pump
Fault
Fault
Neutral from Pump
Live
Neutral
Earth
Low
Pressure
Alarm
Volt Free
240v 0.5 amp
High
Pressure
Alarm
Volt Free
240v 0.5 amp
Used for Pump
Supply
Do not wire to
these terminals
Mains
Supply
240v 50 Hz
10 amps
Charging
Pump
Chassis Base
Earth Tag
Front Door
Earth Tag
Rd
Pp
Pk
Yw
Or
Gy
Br
Or
Wh
Bl
Bk
GY
Bk
Bk
Scale
Scale
Scale
Scale
Cold Fill
Pressure Switch
(Fact ory set ting 1.0 bar)
High Pressure
Alarm Switch
(Fact ory set ting 2.5 bar)
Low Pressure
Alarm Switch
(Fact ory set ting 0.5 bar)
Connection
Details on
Pressure
Switches
BOR
MOR
COM
Hours Run Meter
The High and Low Pressure Alarm switches on this model have been wired to allow Volt Free indication of Faults.
If Power Interruption of the associated Boiler / Chiller plant is required, the 240v 50Hz power supply for the associated
Boiler / Chiller plant should be routed as follows;
Interlock Circuit In
- Term 2
Link Wire Required - Terms 1 & 5
Interlock Circuit Out - Term 6
In this manner if one of the Alarm Switches are activated, the power supply to the associated Boiler / Chiller plant will be
interrupted.