MECHANICAL M1/1 

 

2.0 

Product Description 

PISCES 

MINIFILL 

 

The  Pisces  Minifill  compact  cabinet  housed pressurisation  manager is  suitable  for  maintaining  the  cold fill 

pressure in sealed heating, cooling, or chilled water systems. 

The unit may be wall or floor mounted, and has been designed to meet the needs of the commercial/large 

domestic installations, where plant room space may be restricted. 

 

Wall/Floor mounted with compact dimensions 

At 600mm High, 382mm Wide, and 280mm Deep, the Pisces Minifill pressurisation managers allows for site 

installation where space is of a premium, without compromising serviceability. 

 

Versatility of Use 

With the use of a powerful turbine peripheral pump the Pisces Minifill pressurisation managers can be 

configured to achieve and maintain a system Cold Fill Pressure from as low as 0.8bar up to 3.0bar. 

The unit detailed in this manual utilizes a Type AF Air Gap, and is therefore compatible for use with both 

Fluid Category 3 (C-3) In-House

, and 

Fluid Category 4 (C-4) Other Than In-House 

systems. 

 

Building Management System (BMS) Compatible 

The Pisces Minifill pressurisation manager is supplied as standard with Volt Free Pressure Switches to provide 

remote indication of both High and Low Pressure faults. These switches are rated to accept up to 240Volts AC, 
with a maximum current of 0.5Amps. 

 

Guarantee 

The warranties available on the Pisces Minifill pressurisation manager is as follows; 

 

Supply Only 

Parts Only Warranty, against

 manufacturing or m a t e r i a l  

defects for a period of 12 months from the date of delivery. 

 

Supply and 
Commissioned

 

(By an Elco Engineer)

 

Parts and Labour Warranty, 

against manufacturing  or material  defects 

for  a  period  of  up  to  15  months  from  the date of delivery. 

Содержание M1/1

Страница 1: ...COMPACT WALL MOUNTED PRESSURISATION MANAGER INSTRUCTIONS FOR INSTALLATION SERVICING MAINTENANCE OF THE PISCES MINIFILL MODEL M1 1 Mechanical Single Pump Unit L250 M1 1 PISCES MINIFILL Mechanical Mode...

Страница 2: ...deemed to be competent This manual shall be handed to the unit user following completion of the installation The unit shall not be left to operate without being correctly commissioned Installation Req...

Страница 3: ...and maintain a system Cold Fill Pressure from as low as 0 8bar up to3 0bar The unit detailed in this manual utilizes a Type AF Air Gap and is therefore compatible for use with both Fluid Category 3 C...

Страница 4: ...associated fittings The Pisces Minifill unit cartoncontains Assembled and Tested Pisces Minifill unit Wall mounting bracket Supplied attached to the front of the water tank Installation Template part...

Страница 5: ...d clearances is printed onto the appliance packaging cut along the dotted lines and position the template in the desired location to ensure that all minimum clearances can beachieved The wall mounting...

Страница 6: ...the foul water system The Waste Water Outlet Overflow shall be routed in such a way to minimize the risk of blockage through freezing If any part of the Waste Water Outlet Overflow is to be run extern...

Страница 7: ...Base Earth Tag Front Door Earth Tag Rd Pp Pk Yw Or Gy Br Or Wh Bl Bk GY Bk Bk Scale Scale Scale Scale Cold Fill Pressure Switch Factory setting 1 0 bar High Pressure Alarm Switch Factory setting 2 5 b...

Страница 8: ...C to 115 C 2 0 Max Operating Temp 115 C to 120 C 11 1 Filling the System The Pisces Minifill Mechanical M1 1 pressurisation manager cannot be used to fill the system however the Pisces Minifill Elect...

Страница 9: ...arious safety items associated with the safe operation of the heating cooling chilled water system need to be checked and confirmed We would therefore recommend that a Qualified Gas Safe registered en...

Страница 10: ...ses at the pressure displayed on the appliance pressure gauge Record the Pressure Setting on the Commissioning Form on Page 12 Re connect any Electrical Wires previously removed from Terminals 4 5 6 F...

Страница 11: ...rrect operation and adjust replace as needed Check Setting of HIGH PRESSURE ALARM switch and adjust as needed 14 0 Internal Components Short Parts List Item No Description Part No Cold Fill Pressure S...

Страница 12: ...ty Valve Setting bar Final Working Pressure of System Hot bar High Pressure Alarm Switch Setting bar Low Pressure Alarm Switch Setting bar High Pressure Fault Test Yes No Low Pressure Fault Test Yes N...

Отзывы: