COMPACT, WALL MOUNTED, PRESSURISATION MANAGER 

INSTRUCTIONS FOR INSTALLATION, SERVICING & 

MAINTENANCE OF THE PISCES MINIFILL MODEL 

M1/1 (Mechanical Single Pump) Unit, 

 

 

 

 

 

 

 

 

 

L250-M1/1 

PI

SCES

 M

IN

IF

IL

Me

ch

an

ic

al

 M

ode

 

 

Содержание M1/1

Страница 1: ...COMPACT WALL MOUNTED PRESSURISATION MANAGER INSTRUCTIONS FOR INSTALLATION SERVICING MAINTENANCE OF THE PISCES MINIFILL MODEL M1 1 Mechanical Single Pump Unit L250 M1 1 PISCES MINIFILL Mechanical Mode...

Страница 2: ...deemed to be competent This manual shall be handed to the unit user following completion of the installation The unit shall not be left to operate without being correctly commissioned Installation Req...

Страница 3: ...and maintain a system Cold Fill Pressure from as low as 0 8bar up to3 0bar The unit detailed in this manual utilizes a Type AF Air Gap and is therefore compatible for use with both Fluid Category 3 C...

Страница 4: ...associated fittings The Pisces Minifill unit cartoncontains Assembled and Tested Pisces Minifill unit Wall mounting bracket Supplied attached to the front of the water tank Installation Template part...

Страница 5: ...d clearances is printed onto the appliance packaging cut along the dotted lines and position the template in the desired location to ensure that all minimum clearances can beachieved The wall mounting...

Страница 6: ...the foul water system The Waste Water Outlet Overflow shall be routed in such a way to minimize the risk of blockage through freezing If any part of the Waste Water Outlet Overflow is to be run extern...

Страница 7: ...Base Earth Tag Front Door Earth Tag Rd Pp Pk Yw Or Gy Br Or Wh Bl Bk GY Bk Bk Scale Scale Scale Scale Cold Fill Pressure Switch Factory setting 1 0 bar High Pressure Alarm Switch Factory setting 2 5 b...

Страница 8: ...C to 115 C 2 0 Max Operating Temp 115 C to 120 C 11 1 Filling the System The Pisces Minifill Mechanical M1 1 pressurisation manager cannot be used to fill the system however the Pisces Minifill Elect...

Страница 9: ...arious safety items associated with the safe operation of the heating cooling chilled water system need to be checked and confirmed We would therefore recommend that a Qualified Gas Safe registered en...

Страница 10: ...ses at the pressure displayed on the appliance pressure gauge Record the Pressure Setting on the Commissioning Form on Page 12 Re connect any Electrical Wires previously removed from Terminals 4 5 6 F...

Страница 11: ...rrect operation and adjust replace as needed Check Setting of HIGH PRESSURE ALARM switch and adjust as needed 14 0 Internal Components Short Parts List Item No Description Part No Cold Fill Pressure S...

Страница 12: ...ty Valve Setting bar Final Working Pressure of System Hot bar High Pressure Alarm Switch Setting bar Low Pressure Alarm Switch Setting bar High Pressure Fault Test Yes No Low Pressure Fault Test Yes N...