General Notes 

 

Product Description 

8

 

10.0

 

 

11.0

 

Determining the Cold Fill 
Pressure 
Filling the System 

4

 

3.0

 

Technical Data and Dimensions 

9

 

11.1

 

Introduction of Water 

 

4.0

 

Delivery Consignment / 
Unpacking 

 

 

12.0

 

Treatment 
Commissioning 

 

5.0

 

Locating the Pisces Minifill 

 

12.1

 

First Fill and Setting To Work 

5

 

6.0

 

Installation Clearances 

10

 

13.0

 

Fault Diagnosis 

 

7.0

 

Wall Mounting 

 

11

 

 

14.0

 

 

Internal Components & Short 

6

 

8.0

 

Water Connections 

 

 

Parts List 

 

9.0

 

Electrical Connections 

 

12

 

 

15.0

 

 

Commissioning Form 

7

 

9.1

 

 

Wiring Diagram  

 

 

 

 

 

 

 

 

 

 

1.0 

General Notes 

These  instructions  are  intended  to  assist  the  installer,  commissioning  engineer,  maintenance  engineer  and the 

end user with the usage of the Pisces Minifill (M1/1 Mechanical) pressurisation manager. 

Please  read  this  manual  fully  before  commencing  the  installation  of  the  unit.  The  Pisces  Minifill 

pressurisation  manager  should  only  be  installed  by  persons  deemed  to  be  competent.  This  manual  shall  be 
handed to the unit user following completion of the installation. The unit shall not be left to operate without  being 
correctly commissioned. 

 

Installation Requirements 

The installation of Pisces Minifill pressurisation manager shall be in accordance with the  relevant requirements of 

all current Water Regulations, such as; 

 

Water Supply (Water Fittings) Regulations 1999 (Amended Dec 2000)’, 
Water Byelaws 2000-Scotland, 
Local Water Authority Byelaws, 
IEE Electrical Regulations, 
Health & Safety at Work Act, 
Building Regulations, 
Construction (Design & Management) Regulations 1994, 
National, Fire Regulations, and 
Insurance Company requirements. 

 

The following British Standards / Codes of Practice are also applicable:- 

 

 

BS  6644:  2011  Specification  for gas  fired  hot  water  pressurisation  units of rated inputs  between  60kW 
and 2MW. 

 

BS 6880: 1988  Code of Practice for low temperature hot water heating systems of output greater than 
45kW. Parts 1, 2 & 3. 

 

BS 7593: 1992 Code of Practice for treatment of water in domestic hot water central heating systems. 

 

BS 7671: 1992 Requirements for electrical installations. IEE Wiring Regulations. Sixteenth edition. 

Содержание M1/1

Страница 1: ...COMPACT WALL MOUNTED PRESSURISATION MANAGER INSTRUCTIONS FOR INSTALLATION SERVICING MAINTENANCE OF THE PISCES MINIFILL MODEL M1 1 Mechanical Single Pump Unit L250 M1 1 PISCES MINIFILL Mechanical Mode...

Страница 2: ...deemed to be competent This manual shall be handed to the unit user following completion of the installation The unit shall not be left to operate without being correctly commissioned Installation Req...

Страница 3: ...and maintain a system Cold Fill Pressure from as low as 0 8bar up to3 0bar The unit detailed in this manual utilizes a Type AF Air Gap and is therefore compatible for use with both Fluid Category 3 C...

Страница 4: ...associated fittings The Pisces Minifill unit cartoncontains Assembled and Tested Pisces Minifill unit Wall mounting bracket Supplied attached to the front of the water tank Installation Template part...

Страница 5: ...d clearances is printed onto the appliance packaging cut along the dotted lines and position the template in the desired location to ensure that all minimum clearances can beachieved The wall mounting...

Страница 6: ...the foul water system The Waste Water Outlet Overflow shall be routed in such a way to minimize the risk of blockage through freezing If any part of the Waste Water Outlet Overflow is to be run extern...

Страница 7: ...Base Earth Tag Front Door Earth Tag Rd Pp Pk Yw Or Gy Br Or Wh Bl Bk GY Bk Bk Scale Scale Scale Scale Cold Fill Pressure Switch Factory setting 1 0 bar High Pressure Alarm Switch Factory setting 2 5 b...

Страница 8: ...C to 115 C 2 0 Max Operating Temp 115 C to 120 C 11 1 Filling the System The Pisces Minifill Mechanical M1 1 pressurisation manager cannot be used to fill the system however the Pisces Minifill Elect...

Страница 9: ...arious safety items associated with the safe operation of the heating cooling chilled water system need to be checked and confirmed We would therefore recommend that a Qualified Gas Safe registered en...

Страница 10: ...ses at the pressure displayed on the appliance pressure gauge Record the Pressure Setting on the Commissioning Form on Page 12 Re connect any Electrical Wires previously removed from Terminals 4 5 6 F...

Страница 11: ...rrect operation and adjust replace as needed Check Setting of HIGH PRESSURE ALARM switch and adjust as needed 14 0 Internal Components Short Parts List Item No Description Part No Cold Fill Pressure S...

Страница 12: ...ty Valve Setting bar Final Working Pressure of System Hot bar High Pressure Alarm Switch Setting bar Low Pressure Alarm Switch Setting bar High Pressure Fault Test Yes No Low Pressure Fault Test Yes N...

Отзывы: