background image

 

MECHANICAL M1/1 

 

6.0 

Installation Clearances 

PISCES 

MINIFILL 

 

For ease of installation, commissioning, servicing and maintenance the following clearances should be observed. 

NOTE: These distances are MINIMUM and MUST NOT be reduced. Failure to observe  these 

clearances could result in the warranties on the appliance becoming VOID.

 

 

 

 

7.0 

Wall Mounting 

The Pisces Minifill pressurisation manager can be  floor 

mounted, however it is recommended to be wall mounted,  via 
the wall-mounting bracket supplied.  This bracket  interlocks 
into the cutout on the rear of the appliance. 

A template, detailing the fixing positions and  clearances,  is 

printed  onto  the  appliance  packaging,  cut  along  the  dotted 
lines and position the template in the desired location  to 
ensure that all minimum clearances can be achieved. 

The  wall-mounting  bracket  should  be  securely  fixed  to the 

wall  using  suitable  fixings  for  the  wall  construction  and 
appliance filled weight. The wall-mounting bracket  positioning 
detail is shown in fig 7. 

The Pisces Minifill pressurisation manager should  be carefully 

lifted  so  that  the  cutout  on  the  rear  of  the  Pisces  Minifill 
unit is just above the mounting bracket, and then  gently 
lowered to engage the bracket into the cutout. 

DO NOT 

lift  the 

Pisces Minifill unit by any of the internal parts or components. 

 

Important Notice 

 

When viewed from the side, the North / South axis of  the 

Pisces Minifill unit must be vertical 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig 7 

Содержание M1/1

Страница 1: ...COMPACT WALL MOUNTED PRESSURISATION MANAGER INSTRUCTIONS FOR INSTALLATION SERVICING MAINTENANCE OF THE PISCES MINIFILL MODEL M1 1 Mechanical Single Pump Unit L250 M1 1 PISCES MINIFILL Mechanical Mode...

Страница 2: ...deemed to be competent This manual shall be handed to the unit user following completion of the installation The unit shall not be left to operate without being correctly commissioned Installation Req...

Страница 3: ...and maintain a system Cold Fill Pressure from as low as 0 8bar up to3 0bar The unit detailed in this manual utilizes a Type AF Air Gap and is therefore compatible for use with both Fluid Category 3 C...

Страница 4: ...associated fittings The Pisces Minifill unit cartoncontains Assembled and Tested Pisces Minifill unit Wall mounting bracket Supplied attached to the front of the water tank Installation Template part...

Страница 5: ...d clearances is printed onto the appliance packaging cut along the dotted lines and position the template in the desired location to ensure that all minimum clearances can beachieved The wall mounting...

Страница 6: ...the foul water system The Waste Water Outlet Overflow shall be routed in such a way to minimize the risk of blockage through freezing If any part of the Waste Water Outlet Overflow is to be run extern...

Страница 7: ...Base Earth Tag Front Door Earth Tag Rd Pp Pk Yw Or Gy Br Or Wh Bl Bk GY Bk Bk Scale Scale Scale Scale Cold Fill Pressure Switch Factory setting 1 0 bar High Pressure Alarm Switch Factory setting 2 5 b...

Страница 8: ...C to 115 C 2 0 Max Operating Temp 115 C to 120 C 11 1 Filling the System The Pisces Minifill Mechanical M1 1 pressurisation manager cannot be used to fill the system however the Pisces Minifill Elect...

Страница 9: ...arious safety items associated with the safe operation of the heating cooling chilled water system need to be checked and confirmed We would therefore recommend that a Qualified Gas Safe registered en...

Страница 10: ...ses at the pressure displayed on the appliance pressure gauge Record the Pressure Setting on the Commissioning Form on Page 12 Re connect any Electrical Wires previously removed from Terminals 4 5 6 F...

Страница 11: ...rrect operation and adjust replace as needed Check Setting of HIGH PRESSURE ALARM switch and adjust as needed 14 0 Internal Components Short Parts List Item No Description Part No Cold Fill Pressure S...

Страница 12: ...ty Valve Setting bar Final Working Pressure of System Hot bar High Pressure Alarm Switch Setting bar Low Pressure Alarm Switch Setting bar High Pressure Fault Test Yes No Low Pressure Fault Test Yes N...