PISCES 

MINIFILL 

8.0 

Water Connections

 

The  Mains  Cold  Water  Supply  connection  (A)  shall  be able 

to  supply  at  least  12  litres  per  minute  of  clean  water; 
otherwise the operation of the appliance may empty the  break 
tank of water. 

If the appliance is allowed to be operated  without sufficient 

water,  air  will  be  drawn  into  the  pump  assembly, which 
could result in an Air Lock, and ultimately damage to the pump 
assembly, which would not be covered by  the manufacturing 
warranty.  See Fig 8.1 

 

The Waste Water Outlet/Overflow (B) shall be routed  to  a 

safe discharge location that will not cause harm to  persons, 
nor  property,  but  shall  be  clearly  visible,  so  that  any  water 
discharge will be identified and remedial action  taken, 
ensuring that any wasted water is kept to a minimum. See Fig 
8.1 

MECHANICAL 

M1/1 

The Waste Water Outlet/Overflow shall not be  connected 

directly  to  any  foul  water  system  without  a  suitable  warning 
method being incorporated, as above. 

After the warning method, and before connection to  the  foul 

water system a suitable trap shall be incorporated  to  prevent 
the release of any vapour/effluent from the foul  water system. 

 

The  Waste  Water  Outlet/Overflow  shall  be routed 

in such a way to minimize the risk  of  blockage 
through freezing. If any part of the  Waste Water 
Outlet/Overflow  is  to  be  run  external  to  the 
building or is at risk of freezing, then the pipe  shall 
be suitably insulated to protect against freezing.

 

 

The  System  Connection  (C)  shall  be  connected  to  the 

system pipework in such a manner so that 

the 

suction/discharge pressure of any circulation pumps shall not 
influence the appliance. It is recommended that the  System 
Connection be routed in such a manner to  include/incorporate 
the supply connection to any system expansion vessels.  See 
Fig 8.2 

 

9.0 

Electrical Connection

 

The Pisces Minifill pressurisation manager is  supplied with a 

fly lead for the Mains Power Connection; this cable should not 
be replaced. 

The  appliance  power  supply,  fused  spur  or  fused  plug 

socket, shall be positioned within 1 metre of the unit, See  Fig 
9.0. 

The cable size serving the unit shall be sized in accordance with 

the IEE Electrical Regulation. 

 

After the outer casing has been removed, the  Electrical 

Connection rail can be located on the front-hinged inner door. 

See Fig 9.1 & 9.2, on Page 7, for connections Details. 

 

Please Note the Appliance Serial Number when 

referring to these Connection Details.

 

 

 

 

 

 

 

 

 

 

Fig 8.1 

 
 
 
 
 
 
 
 
 
 
 

 

Fig 8.2 

 

 

   

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Fig 9.0 

Содержание M1/1

Страница 1: ...COMPACT WALL MOUNTED PRESSURISATION MANAGER INSTRUCTIONS FOR INSTALLATION SERVICING MAINTENANCE OF THE PISCES MINIFILL MODEL M1 1 Mechanical Single Pump Unit L250 M1 1 PISCES MINIFILL Mechanical Mode...

Страница 2: ...deemed to be competent This manual shall be handed to the unit user following completion of the installation The unit shall not be left to operate without being correctly commissioned Installation Req...

Страница 3: ...and maintain a system Cold Fill Pressure from as low as 0 8bar up to3 0bar The unit detailed in this manual utilizes a Type AF Air Gap and is therefore compatible for use with both Fluid Category 3 C...

Страница 4: ...associated fittings The Pisces Minifill unit cartoncontains Assembled and Tested Pisces Minifill unit Wall mounting bracket Supplied attached to the front of the water tank Installation Template part...

Страница 5: ...d clearances is printed onto the appliance packaging cut along the dotted lines and position the template in the desired location to ensure that all minimum clearances can beachieved The wall mounting...

Страница 6: ...the foul water system The Waste Water Outlet Overflow shall be routed in such a way to minimize the risk of blockage through freezing If any part of the Waste Water Outlet Overflow is to be run extern...

Страница 7: ...Base Earth Tag Front Door Earth Tag Rd Pp Pk Yw Or Gy Br Or Wh Bl Bk GY Bk Bk Scale Scale Scale Scale Cold Fill Pressure Switch Factory setting 1 0 bar High Pressure Alarm Switch Factory setting 2 5 b...

Страница 8: ...C to 115 C 2 0 Max Operating Temp 115 C to 120 C 11 1 Filling the System The Pisces Minifill Mechanical M1 1 pressurisation manager cannot be used to fill the system however the Pisces Minifill Elect...

Страница 9: ...arious safety items associated with the safe operation of the heating cooling chilled water system need to be checked and confirmed We would therefore recommend that a Qualified Gas Safe registered en...

Страница 10: ...ses at the pressure displayed on the appliance pressure gauge Record the Pressure Setting on the Commissioning Form on Page 12 Re connect any Electrical Wires previously removed from Terminals 4 5 6 F...

Страница 11: ...rrect operation and adjust replace as needed Check Setting of HIGH PRESSURE ALARM switch and adjust as needed 14 0 Internal Components Short Parts List Item No Description Part No Cold Fill Pressure S...

Страница 12: ...ty Valve Setting bar Final Working Pressure of System Hot bar High Pressure Alarm Switch Setting bar Low Pressure Alarm Switch Setting bar High Pressure Fault Test Yes No Low Pressure Fault Test Yes N...

Отзывы: