43
Technical Data
AQUATOP T12C-T19C
1) without
circulating
pump
2) measured value averaged around heat pump (free field)
3) residual delivery pressure is indicated at highest level
Heat Pump Type AQUATOP
T12C
T14C
T19C
Electrical Data
Operating voltage, feed
3 x 400 V
Rated input with B0 / W35
PNT
kW
2.8
3.3
4.0
Ext. fuse
AT
16
20
20
Rated current immersion heater
l max.
A
10,0
10,0
10,0
Rated current heat pump
I max.
A
10,0
12,4
14,0
Current with blocked rotor (LRA)
LRA
A
50
66
Starting current with soft starter
VSA
A
25
27.5
33.8
Power consumption el. immersion heater
max.
kW
6/4/2
Power consumption circulating pumps
max.
kW
0.2
0.3
0.5
Starts per hour
max.
3
3
3
Start delay after power outage
sec.
60-120
Dimensions / Connections / Misc.
Operating weight
kg
Dimensions
WxDxH
mm
670x960x1050 670x960x1050 670x960x1050
Heating circuit connection
IT
inch
1"
1"
1"
Brine circuit connection
IT
inch
1¼"
1¼"
1½"
Sound power level
Lwa
dB(A)
45
48
51
Sound level at 5-m distance 2)
Lpa
dB(A)
27
31
34
Expansion vessel heater
V
l
12
12
2 x 12
Set default pressure heating circuit
p
bar
1,0
1,0
1,0
Expansion vessel brine circuit
V
l
12
12
12
Set default pressure brine circuit
p
bar
0.5
0.5
0.5
Safety valve (brine/heater)
p
bar
3
3
3
Switching point brine pressure monitor
p
bar
0.65
0.65
0.65
74