Initial Startup 
 
 
 
Heat Pump Controller LOGON B RVS51  

RESET 


 
 
 
 

 

 


 
 
 
 

 


Control Based on Atmospheric  
Conditions, Featuring the Following:  

• 

lluminated display, status and  

 

function indicators in plain text. 

• 

Standard program default setting, 

 setpoints, 

date, 

time. 

• 

Automatic switching 

 

between summer/winter time. 

• 

Preset standard timed programs 

 

for heating and hot water heating. 

• 

Complete control and monitoring  

 

of the HP incl. 2 heating circuits  

 

and potable water heating, buffer  

 

in one unit.  

• 

Highly flexible application options 

 

due to wireless transfer to room  

 

controller and exterior sensor  

 (optimal 

for 

renovations). 

• 

Vacation program. 

• 

Info key for quickly querying the 

 

most important temperatures and  

 system 

states. 

• 

Floor drying function. 

• 

Room temperature control with  

 

accessory QAA75 and QAA78. 

• 

Demand-based heater 

 shut-off. 

• 

Easy initial startup of 

 

system due to sensor self-detection  

 

or presetting to specific scheme. 

• 

Adjustable min. and max.  

 flow 

temperatures. 

• 

Pump overrun. 

• 

Integrated operating hours counter. 

 

• 

Thermal disinfection of hot water 

 

with electrical immersion heater in  

 

PWH tank can be enabled in  

 addition. 

• 

2-lead bus interface for 

 controller 

accessories. 

• 

Trend logging 

 (data 

logging 

function). 

 
 
Key: 
 

Operating mode key service  

 water 

 

Switches on potable water heating.  

 

(Bar in display below water faucet.) 

 

Select heating operation

 

 

Sets 4 different heating operating  

 modes. 
 

3 Info 

ke y 

 

Displays information without  

 affecting 

control. 

 

Service plug (BSB)  

 2-wire 

connection. 

 

5 Return 

key 

ESC 

 

Confirmation key OK 

 

These two keys are needed  

 

together with the large rotary knob  

 

(7) for programming and confi- 

 

guring the controller. Settings not  

 adjustable 

with 

the 

control 

 

 

elements are programmed into the  

 control 

unit. 

 
 

Press the ESC key to jump one  

 

step back. Set or adjusted values  

 

are not applied. 

Room temperature control knob,  

 navigation, 

and 

settings 

 - Changes 

the 

 

 

comfort setting of the room. 

 

Use this rotary knob to select  

 

 

and adjust settings during  

  programming. 
 

8 Cool in g 

ke y 

 

Cooling cycle key activates passive  

 

cooling via the heat source for type  

 

AQUATOP T units in combination  

 

with the corresponding accessories. 

 

HP Reset and HP defrosting key  

 

The reset key triggers a reset of  

 

the heat pump. 

Содержание Aquatop TC Series

Страница 1: ...Operating Instructions Only for Authorized Service Technicians Brine Water and Water Water Heat Pumps AQUATOP TC 02 2008 Art No 11 051 525...

Страница 2: ...ging Geothermal Heating Systems Problems and Issues 18 Incorrect Brine Concentration 18 Flushing 18 Charging with Antifreeze 19 Correctly Charging a Geothermal Heating System 19 Initial Startup Heat P...

Страница 3: ...ed in the operating instructions L Comply with information about function and operation E Always comply with and observe all safety notes and safety information Information about the operating instruc...

Страница 4: ...om the brine liquid and returned to the heat exchanger The evaporated working medium is suctioned by the compressor and compressed to a higher pressure The compressed gaseous working medium is fed to...

Страница 5: ...s All guidelines based on CE standards were observed during design and manufacture of the heat pump See CE Conformity Declaration Compliance with the corresponding SEV EN and IEC standards is required...

Страница 6: ...itional items enclosed in accessory bag The following components are included with the heat pump 1 1 Plexiglas cover 2 1 controller receptacle 3 1 front panel 4 1 LOGON B WP controller 5 1 exterior se...

Страница 7: ...ing it Avoid exposing the heat pump to any type of moisture or humidity Also applies to setup and installation Never stack objects on the heat pump or hang up wet clothes over it Setup The heat pump i...

Страница 8: ...damage Properly dispose off the packaging material Transport safety device The flexible connection tubes and hoses included in the delivery scope are attached to the rear of the AQUATOP TC The heating...

Страница 9: ...and safety devces connection lines insulation heat carrier fill Delivery installation by ELCO installation company Probe depth Installed in compact heat pumps Installation and Connection Instructions...

Страница 10: ...Slide valve 3 Intermediate exchanger 4 Manual air exhauster 5 Filling and draining valve 6 Safety valve 7 Thermometer 8 Expansion vessel 9 Manometer 11 Flow monitor 12 Circulating pump 13 Return valve...

Страница 11: ...tructions Heater Side Connection Key 1 Heating water outlet inside thread 2 Heating water inlet inside thread 3 Heat source outlet inside thread 4 Heat source inlet inside thread 5 Electrical feed 6 S...

Страница 12: ...nection without buffer storage comply with min circulating water volume requirement The coil area of the service water storage must be adjusted to the heat pump capacity b Indirect connection with buf...

Страница 13: ...and the safety line of the heating side must be installed freely visible and at an incline towards the building drainage system L The safety line of the heat reclamation side heat gain with brine must...

Страница 14: ...the unit and re moving the cover by pulling towards the top The power supply is carried out via the inlet of the cable connection at the rear side of the heat pump All other neces sary control connec...

Страница 15: ...te input of power element compressor and control element control pumps may be needed Comply with the corresponding connection scheme diagram L Hot cables and sensor cables must be installed separately...

Страница 16: ...to the control panel through the opening in the front upper cover plate Connection Plug to Control Panel 2 Insert Controller Receptacle into Upper Front Cover Plate The controller receptacle is insert...

Страница 17: ...Control Panel into Controller Case Attach Front Cover Insert the front cover panel into the controller case from bottom to top while holding at a slant Snap Front Cover into Place Snap front cover int...

Страница 18: ...lack of the proper equipment to prepare the mixture correctly If the concentration is too high the heat pump s capacity is reduced and works less efficiently The heat pump may also overheat An insuff...

Страница 19: ...l the entire antifreeze mixture except for the 40 liters reserve are filled in and then is switched off at once Excess tap water drains from the drain hose into the drain 9 Now insert the drain hose i...

Страница 20: ...ole inlet and outlet Flushing and charging heating side The heating side must be flushed and charged as well The initial pressure in the diaphragm type expansion vessel heater factory set at 1 bar mus...

Страница 21: ...counter Thermal disinfection of hot water with electrical immersion heater in PWH tank can be enabled in addition 2 lead bus interface for controller accessories Trend logging data logging function Ke...

Страница 22: ...occupancy room after considering the following items Select the placement location in such a way that the sensor is able to obtain accurate room temperature readings and is not affected by direct sun...

Страница 23: ...ntenance special function Error messages Info level activated Setting level activated Heater temporary shut off ECO function active Basic Display Key Level Press OK 1x End user Select desired setting...

Страница 24: ...rating with comfort setpoint Protective mode KON While in protective mode the heater is switched off but remains protected from frost frost protection temperature Adjust room comfort setpoint Use rota...

Страница 25: ...g from comfort setpoint to OFF Switching from cooling OFF to comfort setpoint The presence function only works while in automatic mode The current selection is active until the next switching acc to h...

Страница 26: ...s key 1x and less than 3 seconds Triggers reset Any pending heat pump error messages counters and other resettable para meters are reset all at one when pressing this key The preset switching on delay...

Страница 27: ...arameters Parameter lines E end user and I initial startup are displayed in the initial startup level The complete parameter list with lines E I and F is displayed in the technician level Time and dat...

Страница 28: ...tion operating level 1 HC1 Frost protection Reduced Frost protection Vacation heating circuit 2 652 658 same as vacation heating circuit 1 Vacation heating P 662 668 same as vacation heating circuit 1...

Страница 29: ...ne MC sliding PC absolute Absolute 1640 F Legionella function OFF periodic fixed day of week OFF Heat pumps 2800 I Frost protection condens pump OFF ON ON 2802 I Flow time condens pump s 0 240 10 2803...

Страница 30: ...0 C C 0 20 7 5870 I Combination storage No Yes No 5890 I Relay output QX1 None compressor 2 K2 electrical immers heater flow K26 electrical immers heater buffer K16 None 5891 I Relay output QX2 None c...

Страница 31: ...0 6800 6819 F Time stamp and error code error history 1 18 0 255 Only displays Date time error code error type Maintenance Service 7070 I HP time interval Months 1 240 7071 I HP time since maintenance...

Страница 32: ...I Sensor temperature BX 1 C 28 350 7821 I Sensor temperature BX 2 C 28 350 7822 I Sensor temperature BX 3 C 28 350 7823 I Sensor temperature BX 4 C 28 350 7830 I Sensor temperature BX21 module 1 C 28...

Страница 33: ...441 I Rest level 2 standstill time min min 0 1 255 8442 I Rest level 1 run time min min 0 1 255 8443 I Rest level 2 run time min min 0 1 255 8444 I Rest time limit source temp min min 0 1 65535 8445 I...

Страница 34: ...etpoint cooling 1 C 0 140 8760 I Heating circuit pump Q6 OFF ON 8761 I Heating circuit mixing valve open Y5 OFF ON 8762 I Heating circuit mixing valve open Y6 OFF ON 8770 E Room temperature 2 C 0 50 8...

Страница 35: ...rmediate circuit check plate exchanger for dirt B4 Check flow switch setting triggers too late B5 Check water level in well and check its dropping during operation 107 Hot gas compressor B 81 A Too li...

Страница 36: ...r triggered in cooling circuit A Insufficient flow of brine water in evaporator B Leak in cooling circuit C Pressure controller defective D Plugged filter E Defective or blocked injection valve F Inco...

Страница 37: ...or A3 Recharge brine A4 Check expansion vessel when recharging brine if pressure increases quickly when recharging brine expansion vessel malfunction A5 If occurring several times check brine circuit...

Страница 38: ...0 4 804 19 0 1 268 49 0 421 10 0 4 574 20 0 1 218 50 0 407 9 0 4 358 21 0 1 170 8 0 4 152 22 0 1 125 7 0 3 958 23 0 1 081 6 0 3 774 24 0 1 040 5 0 3 600 25 0 1 000 4 0 3 435 26 0 962 3 0 3 279 27 0 9...

Страница 39: ...urce Outlet Internal thread 1 1 1 4 Heat source Inlet Internal thread 1 1 1 5 Electrical feed PG 13 5 PG 29 6 Sensor cable 7 Safety valve Outlet Brine and heater 8 Controller 9 Controller cover 10 Fro...

Страница 40: ...volume coolant kg 1 4 1 7 1 85 2 0 Geothermal heating system length 50 W m acc to AWP DN 32 m 84 100 126 2 x 74 Evaporator Brine Side Water content WT l 1 5 1 9 1 9 2 4 Volume flow 3 0 K t with B0 W3...

Страница 41: ...0 120 Dimensions Connections Misc Operating weight kg 189 192 193 194 Dimensions WxDxH mm 670x950x1050 670x950x1050 670x950x1050 670x950x1050 Heating circuit connection IT inch 1 1 1 1 Brine circuit c...

Страница 42: ...rge volume coolant kg 2 2 2 4 2 7 Geothermal heating system length 50 W m acc to AWP DN 32 m 2 x 92 2 x 111 3 x 97 Evaporator Brine Side Water content WT l 2 0 2 1 2 4 Volume flow 3 0 K t with B0 W35...

Страница 43: ...onsumption el immersion heater max kW 6 4 2 Power consumption circulating pumps max kW 0 2 0 3 0 5 Starts per hour max 3 3 3 Start delay after power outage sec 60 120 Dimensions Connections Misc Opera...

Страница 44: ...coolant kg 1 75 2 0 Geothermal heating system length 50 W m acc to AWP DN 32 m 1 x 114 2 x 86 Evaporator Brine Side Water content WT l 2 4 2 9 Volume flow 3 0 K t with B0 W35 l h 1818 2743 Volume flow...

Страница 45: ...art delay after power outage sec 60 120 Dimensions Connections Misc Operating weight kg 198 206 Dimensions WxDxH mm 670x950x1050 670x950x1050 Heating circuit connection IT inch 1 1 Brine circuit conne...

Страница 46: ...on glass Air gap heater Heat source brine water Heat source air Electrical setup Glycol charge heat source Frost protection Flow monitor Dewpoint W cooling Frost protection Filter strength ground wate...

Страница 47: ...47 Notes...

Страница 48: ...ELCO GmbH D 64546 M rfelden Walldorf ELCO Austria GmbH A 2544 Leobersdorf ELCOTHERM AG CH 7324 Vilters ELCO Rendamax B V NL 1410 AB Naarden ELCO Belgium n v s a B 1731 Zellik Service...