Commissioning 
 
 
 
Requirements and parameterization 

Introduction

  

 

Commissioning the AEROTOP S heat 
pump can only be carried out by quali-
fied personnel, otherwise the warranty 
shall be forfeit.  
 
It is forbidden to activate the heat 
pump if any of the following conditions 
apply:  

• 

construction drying out; 

 

• 

System temperature < 25 ° C . 
It is recommended  to heat with 
the use of electrical resistance 
installed

 

 

• 

unfinished system (raw con-

struction);

   

• 

external doors and windows 
not completed and closed. In 
these cases, please arrange 
for site heating. Functional 
heating or ready to install with 
the heat pump according to 
DIN EN 1264 is only possible 
when taking into account the 
aforementioned conditions. 
Moreover, please keep in mind 
that after sizing the heat pump 
for normal operation, it may not 
be possible to generate all 
heating necessary.  

 
Please comply also with the following 
instructions:  

• 

Comply with regulations and 
instructions issued by the man-
ufacturer of the screed mortar.   

• 

Correct operations are possi-
ble only with a system that has 
been installed up to standards 
(hydraulics, electrical compo-
nents, settings). Otherwise the 
screed could be damaged.   

 
Before requesting commissioning, the 
following points must be guaranteed 
and checked:  

• 

Regulation box installed and 
fully wired in.  

• 

Heat pump fully connected and 
up to standard, both electrical 
and hydraulic side.   

• 

All components necessary for 
the system to operate, such as 
circulation pumps, three way 
valves, sensors etc, fully con-
nected and up to standard.  

• 

Hydraulic connections fully 
completed and up to standard.  

• 

All sensors installed and up to 
standard, screened and locat-
ed in the correct position on 
the basis of the corresponding 
system layout.  

• 

Heating system built up to 
standard and rinsed, filled and 
deaerated in compliance with 
instructions. Airtight sealing 
check carried out.  

• 

Voltage compliant with the 
values listed on the heat pump 
label.  

• 

All valves in operating position.  

 
To carry out the commissioning, the 
following people must be in attend-
ance:   

• 

Designer: provides the operat-
ing parameters.  

• 

Installer: in charge of function-
ality and regulating the heating 
system.  

• 

System manager (client or 
client's representative): they 
are instructed on the operation 
and use during commissioning.  

 
If the above conditions are not all met 
when the commissioning is request-
ed, ELCO declines all liabilities for 
any running problems of the system. 
In this case the system's commission-
ing is carried out at one's own risk 
and under one's own responsibility.  
 
Parameterization   
of the entire system is managed by 
the integrated LOGON B WP61 regu-
lator. The correct parameter setting is 
detailed in the system documentation.  
 
After commissioning   
After commissioning, the AEROTOP 
S heat pump does not require particu-
lar interventions or adjustments to the 
regulations settings. Any desired ad-
justments to the heating temperatures 
can be carried out on the basis of the 
user instructions for the LOGON B 
WP61 regulator.  

Regulator operation

  

 

The regulation is carried out via ther-
mal sensors and measuring devices 
at the level of heat pump, external air, 
system, accumulator, ACS accumula-
tor and, in case, living room. When 
required, the regulator sends a heat-
ing request to the heat pump.  
 
The heating temperature is regulat-
ed via a characteristic curve. The 
heat pump and system controls are 
automatic. 
The specific system parameters are 
set at the time of commissioning the 
climate regulator.  
 
Warnings

  

 

The AEROTOP S heat pump func-
tions correctly to the extent in which 
the parameters do not differ from the 
expected values. If one or more pa-
rameters are outside the limit values, 
the regulator issues an error via an 
unencoded text and, if necessary, it 
disconnects the heat pump in order to 
protect the various components.  
 
The various warnings are described in 
the user instructions for the LOGON B 
WP61 regulator.  
 
In the presence of certain errors, the 
heat pump is reactivated (automatic 
cancellation) again if the expected 
status was reached again. In general, 
it is also possible to reactivate the 
heat pump manually.  
 

42 

Содержание AEROTOP G

Страница 1: ...Installation operation and maintenance manual AEROTOP G Air Water Heat Pump for installation outdoors 06 2015 Art No 420010405804...

Страница 2: ...mp STRATOS PARA 25 1 9 23 INSTALLATION 24 Transportation General installation notes 24 Pedestal 25 Pipeline Condensate drain pipe 26 Checklist for correct set up 27 Delivery to installation site 28 Hy...

Страница 3: ...ent through the reduction of emissions and the reduced use of primary ener gy In order for your new heating system to function efficiently please observe the following The heat pump system must be siz...

Страница 4: ...installation connection and commissioning of the heat pump must be carried out by a specialised expert in compliance with national appliance regulations and with the instructions for use Any work on...

Страница 5: ...p must be registered with the local power supply company Do not tilt the heat pump more than 15 when transporting Avoid exposing the heat pump to any type of moisture or hu midity Protect the heat pum...

Страница 6: ...if taking into account the aforementioned condi tions After sizing the heat pump for nor mal operations it may not be possi ble to generate all heating neces sary Please comply also with the followin...

Страница 7: ...with copper pipes with aluminium fins The fins have a hydrophilic cov er for better down flow of con densation and optimised de frosting Cooling circuit Hermetically sealed loaded at the factory and t...

Страница 8: ...cket 2 1 switch panel 3 1 control unit to the controller 4 1 outdoor sensor 5 4 vibration absorbent adjustable feet 6 4 hose seals 7 1 set of documentation 8 2 vibration absorbent hoses 9 4 transport...

Страница 9: ...4 40 5 7 COP 2 10 2 10 2 20 1 9 Evaporator air side Evaporator Grooved copper pipes and fins in hydrophilic aluminium Fan Axial Air flow min max m h 3500 4000 4600 2800 5200 Available static pressure...

Страница 10: ...C16A 3 polig C20A 3 polig C25A 3 polig C25A 3 polig Control voltage supply 230V 50Hz Power input data Heat pump max power input without heating element PHP kW 3 17 5 28 6 16 8 20 Heating element power...

Страница 11: ...WP 61 Connections Water inlet DN25 IG 1 DN25 IG 1 DN25 IG 1 DN25 IG 1 Heating water outlet DN25 IG 1 DN25 IG 1 DN25 IG 1 DN25 IG 1 Condensation discharge DN25 IG 1 DN25 IG 1 DN25 IG 1 DN25 IG 1 Power...

Страница 12: ...rator Grooved copper pipes and fins in hydrophilic aluminium Fan axial Air flow min max m h 3500 4000 Available static pressure without ducts Pa 47 45 Min external air temperature in heating C 18 Max...

Страница 13: ...ement 4 kW C40A 1 polig C50A 1 polig External fuse heating element 6 kW A C50A 1 polig C63A 1 polig Control voltage supply 230V 50Hz Power input data Heat pump max power input without heating element...

Страница 14: ...61 Connections Water inlet DN25 IG 1 DN25 IG 1 Heating water outlet DN25 IG 1 DN25 IG 1 Condensation discharge DN25 IG 1 DN25 IG 1 Power supply 1 x 35mm 1 x 35mm Sound power level Lwa 3 nominal power...

Страница 15: ...7 10 15 20 Outlet water temperature C 35 Heating capacity kW 4 41 4 98 5 28 6 36 8 64 9 73 11 91 14 03 Power consumption kW 1 64 1 67 1 70 1 72 1 86 1 89 2 00 2 10 COP 2 69 2 98 3 10 3 69 4 66 5 16 5...

Страница 16: ...erature C 35 Heating capacity kW 6 39 7 22 7 65 9 22 12 52 14 10 17 27 20 34 Power consumption kW 2 37 2 42 2 47 2 50 2 69 2 73 2 90 3 05 COP 2 69 2 98 3 10 3 69 4 65 5 16 5 96 6 68 Outlet water tempe...

Страница 17: ...99 9 36 10 32 11 80 14 10 17 40 20 19 23 14 Power consumption kW 2 94 3 01 3 09 3 24 3 33 3 39 3 52 3 66 COP 2 72 3 11 3 35 3 64 4 23 5 13 5 74 6 32 Outlet water temperature C 45 Heating capacity kW...

Страница 18: ...2 96 3 76 4 09 4 7 4 89 Outlet water temperature C 55 Heating capacity kW 11 96 10 76 7 65 9 55 10 40 11 98 12 60 Power consumption kW 7 06 5 75 3 33 3 28 3 30 3 35 3 36 COP 1 69 1 87 2 30 2 91 3 15...

Страница 19: ...18 96 21 69 24 39 Power consumption kW 5 79 5 87 5 92 6 20 6 26 6 11 6 18 6 22 COP 1 84 2 00 2 15 2 38 2 68 3 10 3 51 3 92 Outlet water temperature C 55 Heating capacity kW 11 96 12 79 14 46 16 18 18...

Страница 20: ...ot allow these values to fall below this threshold Pipelines should be kept as short as possible and be laid in such a way that pressure loss and heat loss are kept to a minimum Poorly or improp erly...

Страница 21: ...4 Fin evaporator CU Aluminium 5 Controls 6 Circulating pump G07 X 7 Electric heating element 2 4 6 KW 8 Condenser heat exchanger ALFA LAVAL 9 Vibration absorbent rubber buffers Diameter 70 mm Height...

Страница 22: ...Technical Data Delivery pressure circulating pump Aerotop G07 X G10 X G07 14M YONOS PARA RS 25 7 5 180 Pumping medium water Media temperature 35 C Density 1000 kg m3 22...

Страница 23: ...Technical Data Delivery pressure circulating pump Aerotop G12 STRATOS PARA 25 1 9 180 Pumping medium water Media temperature 35 C Density 1000 kg m3 23...

Страница 24: ...ifted and transported using only the designated transport aids 4 L sections at the bottom of the unit The AEROTOP G should be set up on level ground and aligned Installation The safety regulations and...

Страница 25: ...wn in figu res The layer thicknesses are average values and have to be adapted to local conditions The rules of construction enginee ring must be observed For pipes that must be included under the hea...

Страница 26: ...harged from the collection tank by means of a tube In the design and installation of the condensate drain you should consider the following points It is necessary to set up the condensate discharge pi...

Страница 27: ...air noise Construction measures can reduce noise plants cannot Use constructional measures to interrupt the spreading of noise from the heat pump direct noise propagation Use solid walls fences palis...

Страница 28: ...Installation Delivery to installation site 2 3 1 n 17 4x 8x M10 4x 4x 28...

Страница 29: ...Installation Delivery to installation site 29...

Страница 30: ...line system of new as well as retrofitted systems must be thoroughly flushed Residue left in the heater pipes will damage the heat exchangers and cause the heat pumps to malfunction It is recommended...

Страница 31: ...Installation Hydraulic connections assembly instructions 3 1 n 3 1 4 2x n 46 1 x 2 1 4 10 x 31...

Страница 32: ...Installation Hydraulic connections assembly instructions 4 7 5 8 4x 1 4 6 2 x 32...

Страница 33: ...thermostatic valves requires approval by the system manager In this case calculate loss of head to determine the wa ter flow For an approximate calculation of the system s minimum volume consider a v...

Страница 34: ...of heat e g chim neys sun flues heating bod ies air currents The power connection of the heat pump must be carried out by qualified personnel and in compliance with national appli ance regulations In...

Страница 35: ...Installation Instruction for the installation of control unit The control unit must be installed indoors temperature range 5 C to 40 C 2 3 1 4x 4x 164 270 2x 35...

Страница 36: ...Installation Instruction for the installation of control unit black wire CL 5 4 36...

Страница 37: ...oller LOGON B WP61 4 Mains supply plug Mains connector phase AC 230 V Main connector neutral connector 5 Contactor electric heating element 6 Circuit breaker 3x400V N 7 Circuit breaker 230V 8 Soft sta...

Страница 38: ...supply plug Mains connector phase AC 230 V Main connector neutral connector 5 Contactor electric heating element 6 Circuit breaker 230V 7 Soft starter and 3 phase relay 8 Thermostat electric heating e...

Страница 39: ...pump controller LOGON B WP61 4 Mains supply plug Mains connector phase AC 230 V Main connector neutral connector 5 Contactor electric heating element AEROTOP G M 6 Circuit breaker 3x400V N 7 Circuit b...

Страница 40: ...92 M19 Fan z UX1 M1 Compressor Q K1 N2 Control unit b G CL CL N1 Controller LOGON B WP61 Condenser pump AEROTOP G X Other important components that have to be wired in the system Description RVS61 plu...

Страница 41: ...regulation temperature sensor y BX5 Condenser pump Descrizione P3 controller connector EEV controller output PB6 Evaporator pressure monitoring J2 J3 GMD 5V B6 PB3 Evaporator temperature sensor J3 B3...

Страница 42: ...ion To carry out the commissioning the following people must be in attend ance Designer provides the operat ing parameters Installer in charge of function ality and regulating the heating system Syste...

Страница 43: ...ce of substances and ad ditives in the heating water can jeop ardise the correct operation and life duration of the heat pump Therefore before replacing the old sys tem heat up the whole system and em...

Страница 44: ...le entry points Terminals Check connections tight Check soft starter amperes and DIP switch set correctly Check rotating field and protective ground conductor Fuses Correct strength Is there energy pr...

Страница 45: ...e bubbles visible Check for any noise compressor running smoothly Check for structure borne noise transmission flexible connection sound absorbing pipe suspension vibration transmission over the floor...

Страница 46: ...0 421 10 0 4 574 20 0 1 218 50 0 407 9 0 4 358 21 0 1 170 8 0 4 152 22 0 1 125 7 0 3 958 23 0 1 081 6 0 3 774 24 0 1 040 5 0 3 600 25 0 1 000 4 0 3 435 26 0 962 3 0 3 279 27 0 926 2 0 3 131 28 0 892 1...

Страница 47: ...34 0 136 60 20 0 12 09 74 0 1 98 33 0 129 70 21 0 11 63 75 0 1 92 32 0 123 20 22 0 11 20 76 0 1 87 31 0 117 10 23 0 10 78 77 0 1 81 30 0 111 30 24 0 10 38 78 0 1 76 29 0 105 70 25 0 10 00 79 0 1 71 2...

Страница 48: ...99 0 0 99 8 0 38 76 46 0 4 74 100 0 0 97 7 0 37 05 47 0 4 59 101 0 0 94 6 0 35 43 48 0 4 44 102 0 0 92 5 0 33 89 49 0 4 30 103 0 0 90 4 0 32 43 50 0 4 16 104 0 0 87 3 0 31 04 51 0 4 02 105 0 0 85 2 0...

Страница 49: ...carried out only by specifically trained technicians Any work carried out on the heat pump by unauthorised persons or companies will result in the loss of any right to warranty Cleaning the condensat...

Страница 50: ...s don t close A3 Heating or potable water circulation pump not running A4 Overflow valve missing or set incorrectly A5 Heating curve set too steep The module switches the particular unit to the safety...

Страница 51: ...njection pipes and compare with B84 value C Switch on electric heating element until the minimum water temperature is reached Close part of heating circuit D Check pumps for functions check return and...

Страница 52: ...Electric heating element should be configured in the program ming menu Heat pump disabled Info about Parameter 8006 status HP 1 Disabled outdoor temperature 2 Disabled external External disablement o...

Страница 53: ...1 152 103 151 110 154 99 155 Warmer climate condition s 172 214 171 213 161 204 154 214 Annual energy consumption Average climate condition QHE 2617 2870 3866 3623 4972 5626 6742 5266 Colder climate c...

Страница 54: ...bivalent temperature Pdh kW 5 0 7 2 9 9 11 1 Tj operation limit temperature Pdh kW 4 2 6 1 7 8 10 3 For air to water heat pumps T j 15 C if TOL 20 C Pdh kW Bivalent temperature Tbiv C 8 8 8 10 Cyclin...

Страница 55: ...to water heat pumps Operation limit tempe TOL C 18 20 Cycling interval efficiency COPcyc 2 55 2 21 Heating water operating limit temperature WTOL C 53 55 Supplementary heater Rated heat output Psup k...

Страница 56: ...Elecromagnetic Compatibility Directive 2010 30 EC Directive on the indication by labelling and standard product information of the consumption of energy and other resources by energy related products...

Страница 57: ...Notes 57...

Страница 58: ...Service www elco net...

Отзывы: