Installation
Electrical Connection
Cable entry points
1
Mains cable entry 230V or 400V
2
Extra-low voltage/sensor cable
entry (24V)
3
Screws
Remove screws (3) and push sheet-
metal cover forward. This makes it
easier to pull in the extra-low voltage/
sensor cables (2). After inserting the
cables,
1
2
3
Power supply to the control panel
The power supply must be
equipped with a device that
allows for complete disconnec-
tion in the conditions of over
voltage III category.
The value of the opening current is
included in the technical data and on
the designation label on the rear of
the heat pump. The power supply
cables (400 V) must be of a suitable
size for the appliance's power in con-
formity with current regulations. Make
provisions for a separate connection
for the heating element. It too must be
equipped with a device that allows for
complete disconnection in the condi-
tions of over voltage III category.
•
Low voltage cables and those
for sensors (24 V) must not be
un in the same conduits or
channels as the supply cables
(400 V).
•
The external regulator sensor
must be installed on an exter-
nal building wall, where it won't
be exposed to the afternoon
sun, nor to other sources of
heat (open windows, chimneys
and similar). If possible,
choose a place facing north or
north-east.
•
In the event of enabling room
sensor via remote control, the
latter must be located in a
reference room (for example
the living room), where it won't
be exposed to extraneous
sources of heat (e.g. chim-
neys, sun, flues, heating bod-
ies, air currents).
The power connection of the
heat pump must be carried out
by qualified personnel and in
compliance with national appli-
ance regulations. In addition, it
is necessary to comply with the
connection conditions of the
local energy provider.
Before any electrical connec-
tion or any operation, you must
always disconnect the power
supply.
Electrical connections and regulat-
ing instructions
The maximum tolerances al-
lowed in the power supply are
2% for frequency and 6% for
voltage.
The heat pump must not be
connected if the difference in
electrical voltage between
phases is over 2%.
Operating outside these limit
values will result in the warran-
ty being forfeit.
If necessary, get in touch with the
local power supplier. The heat pump's
internal cabling is carried out at the
factory in compliance with the electri-
cal layout attached to the appliance.
The heat pump is equipped with an
electrical panel (see image on the
right). To access this panel, remove
the lower front panel.
The power supply cable and the low
voltage cables, for example for sen-
sors, are run from the building to the
heat pump via separate empty tubes.
The electrical panel can be flipped
over to allow access to the rear com-
ponents and for maintenance.
AEROTOP G +
electric heat-
ing element
R25
Ext. fuse
[A]
G07 + R25 2 / 4 / 6
kW
C16
4
G10 + R25 2 / 4 / 6
kW
C20
4
G07X + R25 2 / 4 / 6
kW
32 / 40 / 50
16
G10X + R25 2 / 4 / 6
kW
40 / 50 / 63
16
G12 + R25 2 / 4 / 6
kW
C25
6
G07-14M + R25 2 /
4 / 6 kW
C25
6
Cross-section
terminal board
[mm
2
]
Ext. fuse
[A]
Cross-section
terminal board
[mm
2
]
G07
C13
4
G10
C16
4
G07X
32 / 40 / 50
16
G10X
40 / 50 / 63
16
G12
C20
6
G07-14M
C20
6
AEROTOP
G
34
Содержание AEROTOP G
Страница 28: ...Installation Delivery to installation site 2 3 1 n 17 4x 8x M10 4x 4x 28...
Страница 29: ...Installation Delivery to installation site 29...
Страница 31: ...Installation Hydraulic connections assembly instructions 3 1 n 3 1 4 2x n 46 1 x 2 1 4 10 x 31...
Страница 32: ...Installation Hydraulic connections assembly instructions 4 7 5 8 4x 1 4 6 2 x 32...
Страница 36: ...Installation Instruction for the installation of control unit black wire CL 5 4 36...
Страница 57: ...Notes 57...
Страница 58: ...Service www elco net...