Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-
…
Rev. 1.0
– 29/09/2022
MAEKSN2TP_EN
© Ekinex S.p.A.
– All rights reserved
Pag. 24
14.5 Menus: Alarm function
Although not specified below, these options are only listed if the alarm function is active.
Figure 21 - Alarm function parameters
Parameter name
Conditions
Values [Default]
Duration of one switch-on
window
Device type = Master
0.5 s...60 min
[0.5 s]
Duration of the period in which the specified number of movements (see next parameter) must occur in
order to cause the alarm to be switched ON
Number of switch-on
windows
Device type = Master
0...100 min
[10]
Number of movements in the specified period (
“window”, see previous parameter) that cause the alarm
to be switched ON
Duration of one switch-off
window
Device type = Master
0.5 s...60 min
[0.5 s]
Duration of the period in which the specified number of movements (see next parameter) must occur in
order to cause the alarm to be switched OFF
Number of switch-off
windows
Device type = Master
0...100 min
[10]
Number of movements in the specified period (
“window”, see previous parameter) that cause the alarm
to be switched OFF
Behaviour at switching on
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output when the alarm status is switched to ON.
Behaviour at switching off
lock by communication
object
Device type = Master
No reaction
Switch off
Switch on
Value used as output when the alarm status is switched to OFF.