passing cloud), the detector has been designed with a delay of 10 s for light activation, i.e. it 
will ignore any movement within the 10 s delay time. The red LED will be on steady as an 
indication, but the detector will not react within this timeframe. 

  The  ambient  light  level  changes from  dark to  bright:  if the  ambient  light  level  exceeds  the 

“Switch ON Lux value” for 5 min, there are different reactions according to the value of the 
“Lighting delay time” parameter:  

o

  If Lighting delay time > 5 min: the light will be automatically switched off after 5 min.  

o

 

if Lighting delay time < 5 min: the light will be automatically switched off when the set time 
expires, if no movement is detected within the 5 min. timeframe. But if any movement is 
detected within the 5 min timeframe, the time will be reset upon detection and the light is 
switched off after 5 min.

 

13.9  2-level (Standby Lighting) function 

In Auto mode and when Output type 

is set to “Dimming”, when the ambient light level falls below the 

pre-set 

“Switch ON Lux value”, the detector will enter into 2-level mode function automatically. 

  if 

“Standby Time” is set to “Infinity”, the detector will enter into 2-level mode when the “Lighting 

delay time” is expired. In this situation, if a movement is detected, the load will turn on with 
the  setting  illumination  (100%  or  the  dimmed 

value  according  to  the  setting  of  “Standby 

brightness) and then turn off if movement is no longer detected and the 

“Lighting Delay time” 

has expired. It will be cycled until the ambient light level is higher than the 

“Switch ON Lux 

value

” and it lasts for 5min, then turns off and the detector resumes to Auto mode function. 

 

if  “Standby  Time”  is  set  to  other  position  except  for  “infinity”,  the  detector  behaviour  is 
basically  the  same  as  above  mentioned,  but  the  duration  is  according  to  the  selected 
“Standby Time” value. 

 

If “Lighting standby time” is set to “disable” (OFF), the load will be off when the “Lighting delay 
time

” is expired. 

13.10 Constant light control 

According to the changeable ambient light level, if “Constant light control” is set to Enabled, then the 
load can dim to bright or dark automatically to match the “Preset setpoint” Lux value. 

13.11 Alarm 

The  alarm  function  can  be  set  to  behave  in  the  same  way  in  case  of  switching  on  or  off,  or  in  a 
different way depending on the event. 

The Alarm output (Communication Object 18) can be locked using CO 17 (Lock alarm).  

Options for 

“Behaviour at switching ON (or OFF) lock by CO are “no reaction”, “switch OFF” and 

“switch ON”. 
The number of detected movements 

(“windows”) within a time frame (“Duration”) can be set. 

 

 

Содержание EK-SN2-TP-GAA

Страница 1: ...Application manual KNX standard wall presence detector with movement function EK SN2 TP GAA EK SN2 TP GAE...

Страница 2: ...2 Con guration and commissioning 13 13 Operations 14 13 1 Slide switch setup 14 13 2 Slide switch functions 14 13 3 Walk test 15 13 4 Auto Semi auto mode absence detection function 16 13 5 Test mode 1...

Страница 3: ...standard wall presence detector with movement function EK SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 3 Revision Changes Date Written by Verified by 1 0 First release...

Страница 4: ...aimed at the system configurator as a description and reference of device features and application programming For installation mechanical and electrical details of the device please refer to the tec...

Страница 5: ...depending on the number of trigger events movements detected in a time frame of configurable duration 3 Main features Hidden switch can fit single round or square wall flush mounting box Simple and sa...

Страница 6: ...ort Dimensions 80 x 80 x 31 mm Environmental conditions Operating temperature 20 40 C Relative humidity 95 not condensing 5 Versions The sensor is supplied in 2 versions EK SN2 TP GAA in white color a...

Страница 7: ...Absolute dimming percentage In automatic mode a load connected to a lighting channel will be switched on when movement is detected and if desired the ambient light level is below a preset brightness...

Страница 8: ...MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 8 It is recommended to install the device at a height of 1 2 m 2 0 m The detection range is 9 m at a height of 1 2 m 1 5 m and up to 8 m at a height o...

Страница 9: ...the following conditions during installation Avoid pointing the detector toward objects with highly reflective surfaces such as mirrors glass etc Avoid mounting the detector very close to heat source...

Страница 10: ...SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 10 Layer C masks the area with a circle from about 0m to 1m Figure 6 Layers scheme Cut the supplied shield in such a way to...

Страница 11: ...ully Figure 10 Shield removal 10 Mounting and installation Warning The electrical connection of the device can be carried out only by qualified personnel The incorrect installation may result in elect...

Страница 12: ...l previously connected to the bus cable see Connecting to the KNX bus line in the appropriate seat on the back of the sensor please provide to strip off 5 6mm of cable sheathing by using a tool put th...

Страница 13: ...nd the workshops at KNX certified training centers Con guration and commissioning of the device require the use of the ETS Engineering Tool Software program V5 or later releases These activities must...

Страница 14: ...over of slide switch slightly 2 Turn it upwards to access the switch 3 Once the setting is complete turn the cover downwards in its original position Figure 13 Slide switch access 13 2 Slide switch fu...

Страница 15: ...ow the 60 s warm up time to pass During this timeframe the red LED turns on then turns off after warming up time is expired Set the operating mode to Test via ETS then refer to the following steps Wal...

Страница 16: ...next triggering should be 2 sec interval IMPORTANT The settings of functions described in paragraphs 13 6 13 7 13 8 13 9 and 13 10 are intended for lighting control therefore do not apply to HVAC cont...

Страница 17: ...me is set to Infinity the detector will enter into 2 level mode when the Lighting delay time is expired In this situation if a movement is detected the load will turn on with the setting illumination...

Страница 18: ...for only one of the 4 output channels available When the sensor is configured as slave it can only be used to extend the field of coverage for a master sensor Input slave Device type Master Light out...

Страница 19: ...e Conditions Values Default External switch as ON OFF Dim input Device type Master No Yes If enabled each channel can also be controlled from the KNX bus through communication objects 5 6 7 8 For Ligh...

Страница 20: ...PIR in the device The sensitivity can be adjusted according to user s requirement no matter the detector is master or slave Maximum Highest sensitivity High Higher sensitivity Medium Medium sensitivit...

Страница 21: ...ent brightness Preset setpoint Device type Master Output type Dimming Constant light control enable 10 2000 Lux 300 Lux It is used to set the pre set Lux value for constant light control function i e...

Страница 22: ...ly when the delay time is expired Standby time Device type Master Lux Time etc selected by ETS Lighting standby time enabled 30 s 60 min 5 min It is used to set Auto off time i e the duration of the S...

Страница 23: ...switched ON whenever a movement is detected this is required to prevent immediate activation when a person is present in the coverage area for just a brief period of time HVAC delay time Device type M...

Страница 24: ...of movements in the specified period window see previous parameter that cause the alarm to be switched ON Duration of one switch off window Device type Master 0 5 s 60 min 0 5 s Duration of the period...

Страница 25: ...Switch Yes HVAC Output C3 enabled 1 bit C W 1 001 Switch 8 C4 Manual Input Device type Master External Switch Yes HVAC Output C4 enabled 1 bit C W 1 001 Switch 9 C1 Light Control Output Device type Ma...

Страница 26: ...nction EK SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 26 HVAC Output C4 enabled 17 Lock Alarm Device type Master Alarm function enabled 1 bit C W 1 003 Enable 18 Alarm...

Страница 27: ...ctivating the sensor while doing the test Red LED does not turn on Sensor is not set to Test mode Activate test mode Detection range exceeded Walk in the effective detection range LED indicating funct...

Страница 28: ...cording to following regulations o EN 61000 3 2 o EN 61000 3 3 o IEC EN 61000 6 1 o IEC EN 61000 6 3 o EN 55014 o EN 50491 20 Maintenance The device is maintenance free To clean it use only a dry clot...

Страница 29: ...standards and laws of the respective countries In case of tampering the compliance with the essential requirements of the applicable directives for which the device has been certi ed is no longer guar...

Отзывы: