Application manual
KNX standard wall presence detector with movement function EK-SN2-TP-
…
Rev. 1.0
– 29/09/2022
MAEKSN2TP_EN
© Ekinex S.p.A.
– All rights reserved
Pag. 14
IMPORTANT
:
After a download, it takes approximately 60 s for the sensor to stabilize before it enters
normal operation mode.
Both the light output channels and the red LED are steady ON during the warm-up
phase, and they are switched OFF at the end.
During this settling period, the sensor may not appear to react or perform its programmed
functions.
13
Operations
13.1 Slide switch setup
By using a screwdriver in the center groove (1), pull out the cover of slide switch slightly (2).
Turn it upwards to access the switch (3).
Once the setting is complete, turn the cover downwards in its original position.
Figure 13 - Slide switch access
13.2 Slide switch functions
The slide switch allows to set the following parameters.
AUTO: by placing the switch in the central position, the detector is in AUTO mode.
ON: In ON mode, the load remains ON for 8 hours and the LED flashes for 1 second every
5 seconds. After 8 hours, the detector automatically returns to AUTO mode.
OFF: in the OFF position, the load remains OFF for 8 hours and the LED flashes for 1 second
every 5 seconds. After 8 hours, the detector automatically returns to AUTO mode.
In the event of a power failure, the detector enters AUTO mode once the power is supplied again,
even the switch is set to ON or OFF.
i