Application manual 

KNX standard wall presence detector with movement function EK-SN2-TP-

… 

 

Rev. 1.0 

– 29/09/2022 

 

MAEKSN2TP_EN 

© Ekinex S.p.A. 

– All rights reserved 

 

Pag. 21 

Parameter name 

Conditions 

Values [Default] 

Auto / Semi-auto select 

Device type = Master

 

Auto 

Semi-auto 

It is used to activate / deactivate Auto mode or Semi-auto mode of Light control output C1 or C2. 

The automatic mode controls both switch-on and switch-off; the semi-automatic mode controls switch-off 
after a manual switch-on through the external control pushbutton. 

Output type 

Device type = Master

 

Switching 

Dimming 

It is used to set the output type of detector to be Switching or Dimming. 

Switching mode is used to control an On/Off actuator through a Switch-type object; in this mode, Standby 
function and Constant light control are not available. 

Dimming mode controls a dimming-capable actuator for Absolute brightness, Standby brightness and/or 
Constant rightness, through dedicated Communication Objects. 

Dimming value during ON 
phase 

Device type = Master 

Output type = Dimming

 

1...100% 

[100%]

 

Sets the light output level to switch on, when the channel is active. 

Infinity means that the dimming level is not controlled by Lux value. 

Constant light control 

Device type = Master 

Output type = Dimming

 

Disable 

Enable 

Enables light control function for constant ambient brightness 

Preset setpoint 

Device type = Master 

Output type = Dimming 

Constant light control = enable

 

10...2000 Lux 

[300 Lux]

 

It is used to set the pre-set Lux value for constant light control function, i.e. it sets the target value for 
constant ambient brightness 

Lux deviation 

Device type = Master 

Output type = Dimming 

Constant light control = enable

 

0...255 Lux 

[10 Lux]

 

It is used to set the deviation value of constant dimming function, that is the detector will react refer to 
what the deviation of the ambient light level is. 

This parameters sets the allowed deviation from target value (plus or minus) for constant ambient 
brightness 

Time after switch-on until 
constant light control starts 

Device type = Master 

Output type = Dimming 

Constant light control = enable

 

1 s ... 5 min 

[1 min]

 

It is used to set the standby time before activating the constant light control function after the load is 
switched on. This because after switching the light On, a time period might be necessary for the light to 
warm up or reach a stable condition before brightness regulation starts. 

Switch ON Lux value 

Device type = Master 

Lux / Time etc. selected by = ETS

 

5...2000 Lux 

[2000 Lux]

, Infinity 

Sets the reference brightness for the sensor light level threshold. 

The "Infinity" value disables the threshold, i.e. makes detection independent from light level. 

Lighting delay time 

Device type = Master 

Lux / Time etc. selected by = ETS

 

5 s...60 min 

[5 min]

 

Sets the delay before the output is switched off (or to standby level, if enabled) in absence of detected 
movement. 

Содержание EK-SN2-TP-GAA

Страница 1: ...Application manual KNX standard wall presence detector with movement function EK SN2 TP GAA EK SN2 TP GAE...

Страница 2: ...2 Con guration and commissioning 13 13 Operations 14 13 1 Slide switch setup 14 13 2 Slide switch functions 14 13 3 Walk test 15 13 4 Auto Semi auto mode absence detection function 16 13 5 Test mode 1...

Страница 3: ...standard wall presence detector with movement function EK SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 3 Revision Changes Date Written by Verified by 1 0 First release...

Страница 4: ...aimed at the system configurator as a description and reference of device features and application programming For installation mechanical and electrical details of the device please refer to the tec...

Страница 5: ...depending on the number of trigger events movements detected in a time frame of configurable duration 3 Main features Hidden switch can fit single round or square wall flush mounting box Simple and sa...

Страница 6: ...ort Dimensions 80 x 80 x 31 mm Environmental conditions Operating temperature 20 40 C Relative humidity 95 not condensing 5 Versions The sensor is supplied in 2 versions EK SN2 TP GAA in white color a...

Страница 7: ...Absolute dimming percentage In automatic mode a load connected to a lighting channel will be switched on when movement is detected and if desired the ambient light level is below a preset brightness...

Страница 8: ...MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 8 It is recommended to install the device at a height of 1 2 m 2 0 m The detection range is 9 m at a height of 1 2 m 1 5 m and up to 8 m at a height o...

Страница 9: ...the following conditions during installation Avoid pointing the detector toward objects with highly reflective surfaces such as mirrors glass etc Avoid mounting the detector very close to heat source...

Страница 10: ...SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 10 Layer C masks the area with a circle from about 0m to 1m Figure 6 Layers scheme Cut the supplied shield in such a way to...

Страница 11: ...ully Figure 10 Shield removal 10 Mounting and installation Warning The electrical connection of the device can be carried out only by qualified personnel The incorrect installation may result in elect...

Страница 12: ...l previously connected to the bus cable see Connecting to the KNX bus line in the appropriate seat on the back of the sensor please provide to strip off 5 6mm of cable sheathing by using a tool put th...

Страница 13: ...nd the workshops at KNX certified training centers Con guration and commissioning of the device require the use of the ETS Engineering Tool Software program V5 or later releases These activities must...

Страница 14: ...over of slide switch slightly 2 Turn it upwards to access the switch 3 Once the setting is complete turn the cover downwards in its original position Figure 13 Slide switch access 13 2 Slide switch fu...

Страница 15: ...ow the 60 s warm up time to pass During this timeframe the red LED turns on then turns off after warming up time is expired Set the operating mode to Test via ETS then refer to the following steps Wal...

Страница 16: ...next triggering should be 2 sec interval IMPORTANT The settings of functions described in paragraphs 13 6 13 7 13 8 13 9 and 13 10 are intended for lighting control therefore do not apply to HVAC cont...

Страница 17: ...me is set to Infinity the detector will enter into 2 level mode when the Lighting delay time is expired In this situation if a movement is detected the load will turn on with the setting illumination...

Страница 18: ...for only one of the 4 output channels available When the sensor is configured as slave it can only be used to extend the field of coverage for a master sensor Input slave Device type Master Light out...

Страница 19: ...e Conditions Values Default External switch as ON OFF Dim input Device type Master No Yes If enabled each channel can also be controlled from the KNX bus through communication objects 5 6 7 8 For Ligh...

Страница 20: ...PIR in the device The sensitivity can be adjusted according to user s requirement no matter the detector is master or slave Maximum Highest sensitivity High Higher sensitivity Medium Medium sensitivit...

Страница 21: ...ent brightness Preset setpoint Device type Master Output type Dimming Constant light control enable 10 2000 Lux 300 Lux It is used to set the pre set Lux value for constant light control function i e...

Страница 22: ...ly when the delay time is expired Standby time Device type Master Lux Time etc selected by ETS Lighting standby time enabled 30 s 60 min 5 min It is used to set Auto off time i e the duration of the S...

Страница 23: ...switched ON whenever a movement is detected this is required to prevent immediate activation when a person is present in the coverage area for just a brief period of time HVAC delay time Device type M...

Страница 24: ...of movements in the specified period window see previous parameter that cause the alarm to be switched ON Duration of one switch off window Device type Master 0 5 s 60 min 0 5 s Duration of the period...

Страница 25: ...Switch Yes HVAC Output C3 enabled 1 bit C W 1 001 Switch 8 C4 Manual Input Device type Master External Switch Yes HVAC Output C4 enabled 1 bit C W 1 001 Switch 9 C1 Light Control Output Device type Ma...

Страница 26: ...nction EK SN2 TP Rev 1 0 29 09 2022 MAEKSN2TP_EN Ekinex S p A All rights reserved Pag 26 HVAC Output C4 enabled 17 Lock Alarm Device type Master Alarm function enabled 1 bit C W 1 003 Enable 18 Alarm...

Страница 27: ...ctivating the sensor while doing the test Red LED does not turn on Sensor is not set to Test mode Activate test mode Detection range exceeded Walk in the effective detection range LED indicating funct...

Страница 28: ...cording to following regulations o EN 61000 3 2 o EN 61000 3 3 o IEC EN 61000 6 1 o IEC EN 61000 6 3 o EN 55014 o EN 50491 20 Maintenance The device is maintenance free To clean it use only a dry clot...

Страница 29: ...standards and laws of the respective countries In case of tampering the compliance with the essential requirements of the applicable directives for which the device has been certi ed is no longer guar...

Отзывы: