Application manual 

 

Presence / movement sensors EK-DF2/DG2-TP  

 

Rev. 1.2 - 2020-02-06 

 

MAEKDF2DG2TP_EN 

© Ekinex S.p.A. 

– All rights reserved 

 

Pag. 4 

Product description 

The ekinex

® 

presence sensors 

EK-DF2-TP

 and 

EK-DG2-TP

 are flush-mount ceiling passive infrared 

(PIR) motion detectors, 

for the detection of 

movement / presence of people in indoor environments 

in order to drive lighting and HVAC systems. 

The devices have the same functionality and differ only in the aspects listed below. 

 

 

Throughout the manual, both devices will be referenced indifferently; the respective different 
features will be pointed out wherever required. 

 

The  detection  area,  which  has  a  coverage  angle  of  360°,  can  be  extended  using  other  sensors 
con

figured as slave devices.  

An integrated light sensor, combined with the motion detector, can manage light switching depending 
on brightness level as well as presence. 

The device has two distinct output channels for lighting, with independent parameters; the operation 
can be automatic or semi automatic.  

The device is also capable of maintaining a constant brightness level in the room by controlling a 
dimmable light source. 

All of the above parameters can be set by the user either through ETS or by means of a dedicated 
IR remote during installation. 

The  device  has  two  additional  HVAC  channels,  which  act  in  a  similar  way  as  the  Light  Control 
channels but without the standby time and light level dependence. 

An additional alarm channel can switch the load on or off depending on the number of trigger events 
(movements) detected in a time frame of configurable duration. 

Main features

 

  Semi-automatic or fully automatic operation 

  Two independent Light control channels 

  Two independent HVAC control channels 

  One alarm channel 

  An additional device can be used as slave for any of the channels  

  Detection span of 360°, sectors can be masked through optical shields 

  Adjustable Sensitivity, with "Walk test" to verify detection range 

  Most parameters can be set from ETS or through an IR remote 

Technical data

 

  Rated voltage: 24 Vdc (21 - 30 Vdc) supplied by KNX bus 

  Current consumption (on KNX bus): max 10 mA (operation) / 5 mA (Standby) 

  Detection range: 360° circular (maskable), up to 9m diameter at 2.5m mounting height 

  Light measurement range: 10..2000 Lux 

  Housing, lens and frame in plastic material 

  Safety standards: IEC 61000-6-1 / IEC 61000-6-3 / EN 55014 / EN 50491 

  Dimensions:  

o

  Body diameter Ø 60 mm 

 

Содержание EK-DF2-TP

Страница 1: ...Application manual Indoor presence sensors EK DF2 TP EK DG2 TP...

Страница 2: ...of the detection area 8 9 Installation 9 10 Connection of the KNX bus line 11 11 Con guration and commissioning 11 12 Walk test 12 13 List of ETS parameters 13 13 1 Menu General 13 13 2 Menu Motion s...

Страница 3: ...pplication programming For installation mechanical and electrical details of the device please refer to the technical description datasheet Application manual and application programs for ETS are avai...

Страница 4: ...controlling a dimmable light source All of the above parameters can be set by the user either through ETS or by means of a dedicated IR remote during installation The device has two additional HVAC ch...

Страница 5: ...ls The lighting channel has two operation modes Automatic or Semi automatic The automatic mode controls both switch on and switch off the semi automatic mode only controls switch off after a manual sw...

Страница 6: ...ensor at a standard mounting height of 2 5 m presence detection range for small movements is about 4 meters of diameter while movement detection range person walking through the detection area is abou...

Страница 7: ...ent temperature is close to body temperature In very cold days when heavy clothing is worn especially if the facial area is covered very little heat will be emitted from the body causing the unit to b...

Страница 8: ...pplied optical shielding filters Cut the supplied shield in such a way to remove the sectors corresponding to the desired detection area as in following figure EK DF2 TP EK DG2 TP Apply the shield by...

Страница 9: ...king the electrical connections make sure the power supply has been turned o Warning In order to supply the KNX bus lines use only KNX bus power supplies e g ekinex EK AB1 TP or EK AG1 TP The use of o...

Страница 10: ...carry out the commissioning of the device see Commissioning or at least the download of the physical address using the programming button placed close to the bus connector alternatively programming m...

Страница 11: ...cording to the design of the building automation system done by a quali ed planner For the con guration of the device parameters the corresponding application program or the whole ekinex product datab...

Страница 12: ...n If a further activation of the programming button should become necessary the device can be switched in programming mode through the IR remote available separately 12 Walk test The purpose of the wa...

Страница 13: ...om the slave to one of the device channels Measured Lux value report Disable Enable When enabled the measured ambient brightness value in Lux is transmitted on the bus every 5 s Light control output C...

Страница 14: ...y of the PIR according to user s requirement This setting is available both for master and slave configurations LED turns on when PIR is triggered Disable Enable When enabled the red LED will turn on...

Страница 15: ...tness regulation starts Switch ON Lux value Device type Master Lux Time etc selected by ETS 5 2000 Lux 2000 Lux Infinity Sets the reference brightness for the sensor light level threshold The Infinity...

Страница 16: ...object Device type Master No reaction Switch off Switch on Value used as output when absence of movement presence is detected and confirmed 13 5 Menus Alarm function Although not specified below thes...

Страница 17: ...aster External Switch Yes Light Control Output C1 enabled 1 bit C W 1 001 Switch 6 C2 Manual Input Device type Master External Switch Yes Light Control Output C2 enabled 1 bit C W 1 001 Switch 7 C3 Ma...

Страница 18: ...Control Output C2 enabled 4 bit CR T 3 007 Dimming control 15 C3 HVAC Control Output Device type Master HVAC Output C3 enabled 1 bit CR T 1 001 Switch 16 C4 HVAC Control Output Device type Master HVAC...

Страница 19: ...or while doing the test Red LED does not turn on Sensor is not set to Test mode Activate test mode Detection range exceeded Walk in the effective detection range LED indicating function is set to Disa...

Страница 20: ...ors EK DF2 DG2 TP Rev 1 2 2020 02 06 MAEKDF2DG2TP_EN Ekinex S p A All rights reserved Pag 20 EK DG2 TP EK DG2 TP Sensor Lens shield Instruction sheet 17 Optional accessories EK QR6 IR IR remote contro...

Страница 21: ...vice complies with the Low Voltage Directive 2006 95 EC and the Electromagnetic Compatibility Directive 2004 108 EC Tests carried out according to following regulations o EN 61000 3 2 o EN 61000 3 3 o...

Страница 22: ...nd commissioning of the device can only be carried out by quali ed personnel in compliance with the applicable technical standards and laws of the respective countries In case of tampering the complia...

Отзывы: