Application manual
Presence / movement sensors EK-DF2/DG2-TP
Rev. 1.2 - 2020-02-06
MAEKDF2DG2TP_EN
© Ekinex S.p.A.
– All rights reserved
Pag. 15
Parameter name
Conditions
Values [Default]
Sets the light output level when the channel is active.
Constant light control
Device type = Master
Output type = Dimming
Disable
Enable
Enables light control for constant ambient brightness
Preset setpoint
Device type = Master
Output type = Dimming
Constant light control = enable
10...2000 Lux
[300 Lux]
Sets target value for constant ambient brightness
Lux deviation
Device type = Master
Output type = Dimming
Constant light control = enable
0...255 Lux
[10 Lux]
Allowed deviation from target value (plus or minus) for constant ambient brightness
Time after switch-on until
constant light control starts
Device type = Master
Output type = Dimming
Constant light control = enable
1 s ... 5 min
[1 min]
After switching the light On, a time period might be necessary for the light to warm up or reach a stable
condition before brightness regulation starts.
Switch ON Lux value
Device type = Master
Lux / Time etc. selected by = ETS
5...2000 Lux
[2000 Lux]
, Infinity
Sets the reference brightness for the sensor light level threshold.
The "Infinity" value disables the threshold, i.e. makes detection independent from light level.
Lighting delay time
Device type = Master
Lux / Time etc. selected by = ETS
5 s...60 min
[5 min]
Sets the delay before the output is switched off (or to standby level, if enabled) in absence of detected
movement.
Lighting standby time
Device type = Master
Lux / Time etc. selected by = ETS
Disable
Enable
Enables the standby phase before the output is switched off in absence of detected movement.
Standby time
Device type = Master
Lux / Time etc. selected by = ETS
Lighting standby time = enabled
30 s...60 min
[5 min]
Duration of the Standby phase
Standby brightness
Device type = Master
Lux / Time etc. selected by = ETS
Lighting standby time = enabled
1...60%
[10%]
Light brightness level during the Standby phase
13.4 Menus: HVAC control output C3 / C4
Following parameters are repeated for each of the two HVAC Control channels C3 and C4
.
Although not specified below, these options are only listed if the corresponding channels are active.