Application manual
Presence / movement sensors EK-DF2/DG2-TP
Rev. 1.2 - 2020-02-06
MAEKDF2DG2TP_EN
© Ekinex S.p.A.
– All rights reserved
Pag. 13
13 List of ETS parameters
The paramters available in ETS are the same for both types of sensor..
13.1 Menu: General
Parameter name
Conditions
Values [Default]
Device type
Master
Slave
When the sensor is configured as master, all features are available; it can also receive the trigger signal
from one or more slave sensors for only one of the 4 output channels available.
When the sensor is configured as slave, it can only be used to extend the field od dcoverage for a master
sensor.
Input slave
Device type = Master
Light output C1
Light output C2
HVAC output C3
HVAC output C4
Assign the signal from the slave to one of the device channels.
Measured Lux value report
Disable
Enable
When enabled, the measured ambient brightness value in Lux is transmitted on the bus every 5 s.
Light control output C1
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
Light control output C2
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
HVAC output C3
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
HVAC output C4
Device type = Master
Disable
Enable
Enable the control channel and show the respective group of parameters.
Alarm function
Device type = Master
Disable
Enable
Enable the alarm function and show the respective group of parameters.
13.2 Menu: Motion sensors
Parameter name
Conditions
Values [Default]
External switch
as ON / OFF / Dim input
Device type = Master
No
Yes