UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Troubleshooting
Adira series
68
8.
Troubleshooting
If the UPS system does not operate correctly, first check the operating informa-
tion on the LCD display.
Please attempt to solve the problem using the table below. If the problem still
persists, consult your dealer.
8.1
Troubleshooting according to warning indication
Problem Displayed
Possible cause
Troubleshooting measures
Read EEPROM Error
UPS internal fault.
Consult dealer.
EPO Active
EPO connector is open.
Check the EPO connector
status.
On Maintain Bypass
Maintain bypass switch is
open.
Check the maintain bypass
switch status.
IP softstart failed
UPS internal fault.
Consult dealer.
Site Wiring Fault
Phase and neutral conductor
are reversed at input of UPS
system.
Reverse mains power
wiring.
Battery Disconnect
Battery pack is not connected
correctly.
Do the battery test to confirm.
Check if the battery bank is
connected to the UPS.
Check if the battery breaker is
turned on.
Battery low
Battery voltage is low.
If an audible alarm sounds every
second, the battery is almost
empty.
Output Overload
Overload.
Check the loads and remove
some non-critical loads.
Check if some loads have failed.
Fan Failure
Fan abnormal.
Check if the fan is running nor-
mally.
Charger Fail
Charging fails.
Consult dealer.
Содержание ABADX120009XX600
Страница 83: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Conformity Declarations Adira series 83 Adira 6kVA XL...
Страница 84: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Scope of Delivery Optional Accessories Adira 10kVA...
Страница 85: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Conformity Declarations Adira series 85 Adira 10kVA XL...
Страница 86: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Notes...
Страница 87: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Notes Adira series 87...