UPS Adira (6kVA, 6kVA XL, 10kVA,
10kVA XL 1-phase)
Troubleshooting
Adira series
69
Battery Over Voltage
Battery voltage is higher than
normal value.
Check if the battery quantity is
right.
Over Charge
The battery is over-charged.
The UPS will turn off the charger
until the battery voltage is nor-
mal.
Model Pin Error
UPS internal fault.
Consult dealer.
Ambient Over
Temperature
The ambient temperature is
too high.
Check the environment ventila-
tion.
Heatsink Over
Temperature
The inside temperature of the
UPS is too high.
Check the ventilation of the UPS
and the ambient temperature.
Ambient NTC abnormal
UPS internal fault.
Consult dealer.
Para Cable Male Loss
The parallel cable is discon-
nected.
Check the parallel cable.
Para Cable Female Loss
The parallel cable is discon-
nected.
Check the parallel cable.
Para Bat Differ
The battery packs of some
UPSs are disconnected
Check if all the battery packs are
connected.
Para Line Differ
The mains input of some
UPSs is disconnected.
Check the building wiring and
input cable.
Check if the input breaker is
closed.
Ensure the UPSs are connected
to same input source.
Para Work Mode Differ
There are different power
strategy settings
within a parallel system.
UPSs with different power strat-
egy settings (e.g. one line mode
and one converter mode) are not
permitted in a parallel system.
Para Rate Power Differ
There are different UPSs in
parallel system.
UPSs with different capacity
(e.g. one 6KVA and one 10KVA)
are not permitted in a parallel
system.
ECO In Para
HE (High Efficiency) function
is activated in a parallel sys-
tem.
HE (High Efficiency) function is
not permitted in parallel system.
IP Fuse Open
Input fuse break.
Check the input fuse status.
8.2
Troubleshooting according to fault indication
Problem Displayed
Possible cause
Troubleshooting measures
Inv Overload Fault
Overload.
Check the loads and remove
some non-critical loads.
Check if some loads have failed.
Byp Overload Fault
Overload.
Check the loads and remove
Содержание ABADX120009XX600
Страница 83: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Conformity Declarations Adira series 83 Adira 6kVA XL...
Страница 84: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Scope of Delivery Optional Accessories Adira 10kVA...
Страница 85: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Conformity Declarations Adira series 85 Adira 10kVA XL...
Страница 86: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Notes...
Страница 87: ...UPS Adira 6kVA 6kVA XL 10kVA 10kVA XL 1 phase Notes Adira series 87...